84 RT-SVP07B-EN
SETUP Menu
SZVAV Cooling Control Gains
Proportional 6.0 %/F Reset Time 1200 Sec
Used With: All IntelliPak units with
SZVAV Installed.
Factory Preset:
Prop: 6.0
Reset: 1200
Possible Values:
Prop: 0.2 - 50
Reset: 90 - 3600, DISABLED
Note: This screen must be changed on field replacement of the
RTM Module.
• Press Next/Previous keys to navigate.
SZVAV Heating Control Gains
Proportional 8.0 %/F Reset Time 1200 Sec
Used With: All IntelliPak units with
SZVAV Installed.
Factory Preset:
Prop: 8.0
Reset: 1200
Possible Values:
Prop: 0.2 - 50
Reset: 90 - 3600, DISABLED
Note: This screen must be changed on field replacement of the
RTM Module.
• Press Next/Previous keys to navigate.
Zone Control Occupied Heating Gains
Proportional 30.0 %/F Reset Time 1800 Sec
Used With: All IntelliPak units with
Staged Heat Installed.
Range: 2.0 - 200
Possible Values:
[See “Table 6. Proportional Parameter -
Staged Heat" on page 84 for
assignments.]
Note: This screen must be changed on field replacement of the
RTM Module.
Table 6. Proportional Parameter - Staged Heat
Product
Staged Heat
Type No of Stages
Proportional
Gain
IPak I Gas 2 30.0
IPak I Electric 3 45.0
IPak II Gas 2 30.0
IPak II Electric 90 kw 3 45.0
IPak II Electric 140 kw 4 60.0
IPak II Electric 265 kw 5 75.0
IPak II Electric 300 kw 5 75.0
• Press Next/Previous keys to navigate.
Rapid DX Interstage Timing: 30 Sec
Used With: All IntelliPak units w/
Dehumidification or Rapid Restart.
Factory Presets: Range: 30
Possible Values: 15 - 50
Note: This screen must be changed on field replacement of the
RTM Module.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.