SETPOINT Menu
Default Design Min OA Flow Stp: 350 CCFM
Default DCV Min OA Flow Setpt: 150 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV
Factory Preset: 220 CCFM
Ovrd to 112 CCFM for 90 and 105 Ton
Ovrd to 146 CCFM for 120 and 130 Ton
Possible Values:
Design Min OA Flow: 0 to 585 CCFM
DCV Min OA Flow: 0 to 585 CCFM
• Press Next/Previous keys to navigate.
Demand Controlled Ventilation
Min OA Flow deadband: 5 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV
Factory Presets: 5 CCFM
Possible Values: 5 to 20 CCFM
• Press Next/Previous keys to navigate.
OR
Note: The following screen is only shown if DCV is disabled.
Default Min OA Flow Setpoint: 40 CCFM
Min OA Flow Deadband: 5.0 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/o DCV
Factory Presets:
Setpoint: 40 CCFM
Deadband: 5 CCFM
Possible Values:
[See “Table 7. Max Unit Airflows” for
assignments.]
Table 7. Max Unit Airflows
Product
Capacity
(Tons)
Max Airflow
Range
(CFM)
Deadband
Range
(CFM)
IPak 20 to 25 0 to 14000 500 to 2000
IPak 30 0 to 17000 500 to 2000
IPak 40 0 to 22000 500 to 2000
IPak 50 to 55 0 to 28000 500 to 2000
IPak 60 to 75 0 to 33000 700 to 2000
IPak 90 to 130 0 to 46000 1000 to 2000
IPak II 90 to 105 0 to 45000 500 to 2000
IPak II 120 to 150 0 to 58500 500 to 2000
• Press Next/Previous keys to navigate.