RT-SVP07B-EN 93
SETPOINT Menu
Exhaust Enable Point. Enable Exhaust Fan
When Outside Air damper is Above: 25%
Used With: Units w/Power Exhaust
Option
Factory Presets: 25 %
Possible Values: 0 to 100 %
• Press Next/Previous keys to navigate.
Exhaust Disabled When OA Damper is Below
Exhaust Inhibit Point: 15%
Used With: Units w/Power Exhaust, w/
Return Fan Option
Factory Presets: DISABLED
Possible Values: 0 to 25 %, DISABLED
“Exhaust Disabled When OA Damper is Below” is shown when set
to anything other than DISABLED. If set to DISABLED, “Exhaust
Function Not Disabled By” is shown on top line.
• Press Next/Previous keys to navigate.
Low Ambient Comp Lockout Temp: 50°F
Comp(s) OFF if OA Temp Below This Value
Used With: Units w/DX Cooling
Factory Presets: 50ºF
Possible Values: -20 to 80ºF
• Press Next/Previous keys to navigate.
For Standby Freeze Avoidance, Open the
Hydronic Heat Valve(s) To: 0%
Used With: Units w/Hydronic Heat
Factory Preset: Disabled
Possible Values: Disabled, 1 to 100 %
Note: When the supply fan is OFF, and the active outside air
temperature drops below 45F, the hydronic valve output will be
driven to the value specified here.
• Press Next/Previous keys to navigate.
Frost Avoidance ON When LRE Temp Below
Recovery Frost Avoidance Setpoint: 27°F
Used With: Units w/Energy Recovery
Option
Factory Preset: 27ºF
Possible Values: 0 to 60ºF
• Press Next/Previous keys to navigate.
SETPOINT SOURCE SELECTIONS SUBMENU SCREENS
Setpoint Source Selections Submenu
Press ENTER to Review or Adjust
Used With: All Units
Factory Presets: For All Setpoint
Source Selections the Factory Presets will
be:
HI (KEYPAD) SETPOINT MENU
Note: For GBAS selections to be shown, either the GBAS(5VDC) or
GBAS(10VDC) module must be installed.
• Press the Next key to skip this Submenu.