98 RT-SVP07B-EN
CONFIGURATION Menu
Configuration - Model Num Digit 2
Heating Type: GAS
Used With: All Units.
Possible Values:
ELECTRIC
GAS
HYDRONIC
EXTERNAL HEAT
NONE (COOLING ONLY) Press Next/Previous keys to navigate.
Configuration - Model Num Digit 5, 6, 7
Unit Capacity: 90
Used With: All Units w/DX Cooling
Possible Values:
Multiple Selections: 20 through 162
Tons
OR
Configuration - Model Num Digit 5, 6, 7
Unit Capacity CFM: 16100-45000
Used With: Air Handler Units w/o DX
Cooling
Possible Values:
Multiple Selections: 4000 through
45000
Press Next/Previous keys to navigate.
Configuration - Model Num Digit 6
Cooling Type: NO COOLING
Used With: Air Handler Units
Possible Values:
NO COOLING
DX COOLING
CHILLED WATER Press Next/Previous keys to navigate.
Configuration - Model Num Digit 9
Electric Heat Capacity: 90 KW
Used With: Units w/Electric Heat Option
Possible Values:
30, 50, 70, 110, 130, 150, 170, 190 KW
OR
Configuration - Model Num Digit 9
Gas Heat Type: STAGED
Used With: Units w/Gas Heat Option
Possible Values:
STAGED
MODULATING Press Next/Previous keys to navigate.
Configuration - Model Num Digit 17 or 11
Exhaust/Return: NONE
Used With: All Units
Possible Values:
NONE
EXH FAN_W/ STATITRAC
EXH FAN_W/O STATITRAC
RET FAN W/ STATITRAC
RET FAN W/O STATITRAC
Note: “RET FAN…” (All Return Fan) selections are not permitted to
be installed here if the “Energy Recovery” option below is set to
INSTALLED.
Press Next/Previous keys to navigate.