Table 2. Thermostat Installer Setup Options (Continued).
Installer
Setup Number
Factory-Setting
Other Choices
(Press ▲ or ▼ key to change)
Select Display Description Display Description
Minimum deadband
between heating and
cooling in auto
changeover mode
30 04 Heating and cooling
setpoints can be set no
closer than 4°F (2°C)
03 thru
10
Heating and cooling
setpoints can be set no
closer than the chosen
value:
3—3°F (1.5°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
Minimum on time (heat) 32 10 Ten-minute minimum on
time for compressor
(heating)
00 thru
15
Minimum number of minutes
(0 thru 15) the compressor is
on during call for heat
Minimum on time
(cooling)
33 10 Ten-minute minimum on
time for compressor
(cooling)
00 thru
15
Minimum number of minutes
(0 thru 15) the compressor is
on during call for cool
Temperature range stops
in heating
34 85 Highest heating
sepoint setting
55 to
85
Temperature range (1°F
increments) of heating
stpoint setting
Temperature range stops
in cooling
35 65 Lowest cooling
sepoint setting
65 to
99
Temperature range (1°F
increments) of cooling
stpoint setting
Temperature display
adjusment
37 00 No difference in
displayed temperature
and actual room
temperature.
3, 2, 1,
-1, -2,
or -3
3—Display adjusts to 3°F
higher than actual room
temperature.
2—Display adjusts to 2°F
higher than actual room
temperature.
1—Display adjusts to 1°F
higher than actual room
temperature.
-1—Display adjusts to 1°F
lower than actual room
temperature.
-2—Display adjusts to 2°F
lower than actual room
temperature.
-3—Display adjusts to 3°F
lower than actual room
temperature.
Minimum off time (heat) 38 05 Five-minute minimum off
time for the heating.
00 thru
15
Minimum number of minutes
(0 thru 15) the compressor is
off between calls for heat.
Minimum off time
(cooling)
39 05 Five-minute minimum off
time for the heating.
00 thru
15
Minimum number of minutes
(0 thru 15) the compressor is
off between calls for cool.
Cooling Droop 41 01 Cooling droop activated 00 No cooling droop