RT-SVX25C-EN 27
Installation
3. Do not run the electrical wires transporting DC signals in or around conduit housing high
voltage wires.
Table 4. Zone sensor module wiring
Distance from Unit
to Control
Recommended Wire
Size
0 - 150 feet 22 gauge
0 - 45.7 m .33 mm2
151 - 240 feet 20 gauge
46 - 73.1 m .50 mm2
241 -385 feet 18 gauge
73.5 - 117.3 m .75 mm2
386 - 610 feet 16 gauge
117.7 - 185.9 m 1.3 mm2
611 - 970 feet 14 gauge
186.2 - 295.7 m 2.0 mm2
Figure 13. Reliatel refrigeration module