EasyManua.ls Logo

Trane THT02775 - System Lockout; To Lock the Thermostat; To Unlock the Thermostat

Trane THT02775
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAS-SVX44A-EN 41
Other Thermostat Functions
Table 9. Remote humidity sensor: Current/voltage versus humidity
System Lockout
The thermostat can be locked out to prevent unauthorized personnel from changing settings. A
lockout will disable changes to the following modes: System, Fan, Scheduling, Time, and TOV. If
a change attempt is made, the lock icon ( ) will blink (1 Hz, 20/80%) for 10 seconds on the LCD
display and then go solid again.
To lock the thermostat:
Simultaneously touch and hold both setpoint increment/decrement arrows for 4 seconds as
shown below. When the mode is locked, the lock icon ( ) blinks (1 Hz, 20/80%) for 5 seconds
and then goes solid.
To unlock the thermostat:
Simultaneously touch and hold both increment/decrement arrows for 4 seconds. When the
mode is unlocked, the lock icon ( ) will disappear.
Current (mA) Voltage Relative Humidity Range % (±)
4 1 (Estimated)0
4.8 1.2 (Estimated)5
5.6 1.4 10 0.5
7.2 1.8 20 0.5
8 2 (Low Calibration Point) 25 0.5
10.4 2.6 40 1.0
12 3 50 1.0
16 4 (High Calibration Point) 75 1.5
18.4 4.6 90 1.5
19.2 4.8 (Estimated) 95
20 5 (Estimated) 100