77
Bus Bus Setup/Preset Setup/Preset Setup No.
Msb Lsb Msb Lsb Preset Ref. No.
00 0 0 1
00 0 1 1
00 1 0 1
00 1 1 1
01 0 0 2
01 0 1 2
01 1 0 2
01 1 1 2
10 0 0 3
10 0 1 3
10 1 0 3
10 1 1 3
11 0 0 4
11 0 1 4
11 1 0 4
11 1 1 4
507 Selection of Setup
(SELECTING OF SETUP)
508 Selection of Preset Reference
(SELECTING OF SPEED)
Value:
Digital input (DIGITAL INPUT) [0]
Serial communication (SERIAL PORT) [1]
Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
See the functional description for parameters 507 and 508 under
parameter 503, Coasting Stop.
Description of choice:
The table below shows the Setup (parameter 002 Active Setup) that
has been selected via Digital input, Serial communication, Logic and or
Logic or. The table also shows the preset reference (parameters 211
through 214, Preset reference) that has been selected via Digital
input, Serial communication, Logic and or Logic or.
Digital Input
Bus Bus Setup/Preset Setup/Preset Setup No.
Msb Lsb Msb Lsb Preset Ref. No.
00 0 0 1
00 0 1 2
00 1 0 3
00 1 1 4
01 0 0 1
01 0 1 2
01 1 0 3
01 1 1 4
10 0 0 1
10 0 1 2
10 1 0 3
10 1 1 3
11 0 0 1
11 0 1 2
11 1 0 3
11 1 1 4
506 Reversing
(REVERSING)
Value:
Digital input (DIGITAL INPUT) [0]
Serial communication (SERIAL PORT) [1]
Logic and (LOGIC AND) [2]
Logic or (LOGIC OR) [3]
Function:
See the functional description under parameter, 503 Coasting Stop.
Description of choice:
The table below shows when the motor is running forward and reverse
when Digital input, Serial communication, Logic and or Logic or has
been selected.
Logic and
Bus Bus Setup/Preset Setup/Preset Setup No.
Msb Lsb Msb Lsb Preset Ref. No.
00 0 0 1
00 0 1 1
00 1 0 1
00 1 1 1
01 0 0 1
01 0 1 2
01 1 0 1
01 1 1 2
10 0 0 1
10 0 1 1
10 1 0 3
10 1 1 3
11 0 0 1
11 0 1 2
11 1 0 3
11 1 1 4
Serial Communication
Digital Input Serial Communication
Serial Serial
Term. 19 Comm. Function Term. 19 Comm. Function
0 0 Forward 0 0 Forward
0 1 Forward 0 1 Forward
1 0 Reverse 1 0 Forward
1 1 Reverse 1 1 Reverse
Logic and Logic or
Serial Serial
Term. 19 Comm. Function Term. 19 Comm. Function
0 0 Forward 0 0 Forward
0 1 Forward 0 1 Reverse
1 0 Forward 1 0 Reverse
1 1 Start 1 1 Reverse
Indicates factory default setting. Numbers in brackets [ ] represent selection as displayed on the serial bus.