1-63 Slip Compensation Time Constant
Range: Function:
0.1 s
*
[0.05 - 5 s] Enter the slip compensation reaction speed.
A high value results in slow reaction, and a
low value results in quick reaction. If low-
frequency resonance problems occur, use a
longer time setting.
1-64 Resonance Dampening
Range: Function:
100
%
*
[0 -
500 %]
Enter the resonance damping value. Set
parameter 1-64 Resonance Dampening and
parameter 1-65 Resonance Dampening Time
Constant to help eliminate high-frequency
resonance problems. To reduce resonance
oscillation, increase the value of
parameter 1-64 Resonance Dampening.
1-65 Resonance Dampening Time Constant
Range: Function:
0.005 s
*
[0.001 -
0.050 s]
Set parameter 1-64 Resonance Dampening
and parameter 1-65 Resonance Dampening
Time Constant to help eliminate high-
frequency resonance problems. Enter the
time constant that provides the best
dampening.
1-66 Min. Current at Low Speed
Range: Function:
50 %
*
[0 - 120 %] Applies to PM motors only. Increasing the
minimum current improves motor torque at
low speed, but also reduces
eciency.
3.2.9 1-7* Start Adjustments
Parameters for
conguring
special motor start features.
1-70 PM Start Mode
This parameter is valid since software version 2.80 and later
versions. Use this parameter to select the PM motor start mode,
which is to initialize the VVC
+
control core for previously free-
running PM motors. This parameter is active for PM motors in
VVC
+
mode only if the motor is stopped (or running at low
speed).
Option: Function:
[0] Rotor Detection The rotor detection function estimates the
electrical angle of the rotor and uses the
angle as a starting point. This option is
the standard selection for automation
frequency converter applications. If the
ying start function detects that motor is
running at low speed or is stopped, the
frequency converter can detect the rotor
position (the angle). The frequency
1-70 PM Start Mode
This parameter is valid since software version 2.80 and later
versions. Use this parameter to select the PM motor start mode,
which is to initialize the VVC
+
control core for previously free-
running PM motors. This parameter is active for PM motors in
VVC
+
mode only if the motor is stopped (or running at low
speed).
Option: Function:
converter then starts the motor from that
angle.
[1]
*
Parking The parking function applies DC current
across the stator winding, and rotates the
rotor to electrical zero position. This
function is typically selected for HVAC
applications. If the
ying
start function
detects that motor is running at low
speed or is stopped, the frequency
converter sends out a DC current to park
the motor at an angle. The frequency
converter then starts the motor from that
angle.
1-71 Start Delay
Range: Function:
0 s
*
[0 - 10
s]
This parameter enables a delay of the starting
time. The frequency converter begins with the
start function selected in parameter 1-72 Start
Function. Set the start delay time until
acceleration is to begin.
1-72 Start Function
Option: Function:
[0] DC Hold/
delay time
The motor is energized with
parameter 2-00 DC Hold/Motor Preheat
Current during start delay time.
[2]
*
Coast/delay
time
The is coasted during start delay time ( o).
Parameters TR150 and TR170
36 02/2017 All rights reserved. BAS-SVP16B-EN