EasyManua.ls Logo

Trane TR150 - Page 54

Trane TR150
121 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to
dene
the function of the relays.
The selection of each mechanical relay is realized in an array
parameter. When parameter 0-03 Regional Settings is set to [0]
International, the default value is [9] Alarm; When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [160] No alarm.
Option: Function:
[193] Sleep Mode The frequency converter/system has
turned into sleep mode. See parameter
group 22-4* Sleep Mode.
[194] Broken Belt
Function
A broken-belt condition has been
detected. Enable the function in
parameter 22-60 Broken Belt Function.
[196] Fire Mode The frequency converter is operating in
re mode. See parameter group 24-0* Fire
Mode.
[198] Drive Bypass To be used as a signal for activating an
external electromechanical bypass,
switching the motor directly on line.
See parameter group 24-1* Drive Bypass.
5-41 On Delay, Relay
Array [2]
Range: Function:
0.01 s
*
[0.01 -
600 s]
Enter the delay of the relay cut in time.
Select 1 of 2 internal mechanical relays in an
array function. See parameter 5-40 Function
Relay for details.
Illustration 3.7 On Delay, Relay
5-42 O Delay, Relay
Array[2]
Range: Function:
0.01 s
*
[0.01 -
600 s]
Enter the delay of the relay cutout time. Select
1 of 2 internal mechanical relays in an array
function. See parameter 5-40 Function Relay for
details. If the selected event condition changes
before a delay timer expires, the relay output
is unaected.
Illustration 3.8 O Delay, Relay
If the selected event condition changes before the on
delay or o delay timer expires, the relay output is
unaected.
3.6.4 5-5* Pulse Input
The pulse input parameters are used to
dene
an
appropriate window for the impulse reference area by
conguring
the scaling and
lter
settings for the pulse
inputs. Input terminals 29 or 33 act as frequency reference
inputs. Set terminal 29 (parameter 5-13 Terminal 29 Digital
Input) or terminal 33 (parameter 5-15 Terminal 33 Digital
Input) to [32] Pulse input. If terminal 29 is used as an input,
set parameter 5-01 Terminal 27 Mode to [0] Input.
Illustration 3.9 Pulse Input
Parameters Programming Guide
BAS-SVP16B-EN 02/2017 All rights reserved. 53
3
3

Table of Contents

Other manuals for Trane TR150

Related product manuals