5-50 Term. 29 Low Frequency
Range: Function:
20 Hz
*
[20 -
31999 Hz]
Enter the low frequency limit
corresponding to the low motor shaft
speed (that is low reference value) in
parameter 5-52 Term. 29 Low Ref./Feedb.
Value. See Illustration 3.9.
5-51 Term. 29 High Frequency
Range: Function:
32000
Hz
*
[21 -
32000 Hz]
Enter the high frequency limit
corresponding to the high motor shaft
speed (that is high reference value) in
parameter 5-53 Term. 29 High Ref./Feedb.
Value.
5-52 Term. 29 Low Ref./Feedb. Value
Range: Function:
0
*
[-4999 -
4999 ]
Enter the low reference value limit for the
motor shaft speed [RPM]. This is also the lowest
feedback value. Set terminal 29 to digital input
(parameter 5-13 Terminal 29 Digital Input =
applicable value).
5-53 Term. 29 High Ref./Feedb. Value
Range: Function:
Size
related
*
[-4999 -
4999 ]
Enter the high reference value [RPM] for
the motor shaft speed and the high
feedback value. Select terminal 29 as a
digital input (parameter 5-13 Terminal 29
Digital Input = applicable value).
3.6.5 5-9* Bus Controlled
This parameter group selects digital and relay outputs via a
eldbus
setting.
5-90 Digital & Relay Bus Control
Range: Function:
0
*
[0 - 0xFFFFFFFF ] This parameter holds the state of the bus-
controlled digital outputs and relays.
A logical 1 indicates that the output is
high or active.
A logical 0 indicates that the output is
low or inactive.
Bit 0–3 Reserved
Bit 4 Relay 1 output terminal
Bit 6–23 Reserved
Bit 24 Terminal 42 digital output
Bit 26–31 Reserved
Table 3.5 Bit Functions