6-12 Terminal 53 Low Current
Range: Function:
4 mA
*
[0 - 20
mA]
Enter the low current value. This reference
signal corresponds to the low reference/
feedback value that is set in
parameter 6-14 Terminal 53 Low Ref./Feedb.
Value. To activate parameter 6-01 Live Zero
Timeout Function, set the value to >2 mA.
6-13 Terminal 53 High Current
Range: Function:
20 mA
*
[0 - 20
mA]
Enter the high current value corresponding
to the high reference/feedback set in
parameter 6-15 Terminal 53 High Ref./Feedb.
Value.
6-14 Terminal 53 Low Ref./Feedb. Value
Range: Function:
0
*
[-4999 -
4999 ]
Enter the reference or feedback value that
corresponds to the voltage or current set in
parameter 6-10 Terminal 53 Low Voltage to
parameter 6-12 Terminal 53 Low Current.
6-15 Terminal 53 High Ref./Feedb. Value
Range: Function:
Size
related
*
[-4999 -
4999 ]
Enter the reference or feedback value
that corresponds to the voltage or
current set in parameter 6-11 Terminal
53 High Voltage to
parameter 6-13 Terminal 53 High
Current.
6-16 Terminal 53 Filter Time Constant
Range: Function:
0.01 s
*
[0.01 - 10
s]
Enter the time constant. This constant is a
rst-order
digital low-pass
lter
time
constant for suppressing electrical noise in
terminal 53. A high time constant value
improves dampening, but also increases the
time delay through the lter.
6-19 Terminal 53 mode
Option: Function:
Select whether terminal 53 is used for
current or voltage input.
[0] Current mode
[1]
*
Voltage mode
3.7.3 6-2* Analog Input 54
Parameters for conguring the scaling and limits for analog
input 54 (terminal 54).
6-20 Terminal 54 Low Voltage
Range: Function:
0.07 V
*
[0 - 10
V]
Enter the voltage (V) that corresponds to the
low reference value (set in
parameter 6-24 Terminal 54 Low Ref./Feedb.
Value). To activate parameter 6-01 Live Zero
Timeout Function, set the value at >1 V.
6-21 Terminal 54 High Voltage
Range: Function:
10 V
*
[0 - 10 V] Enter the voltage (V) that corresponds to the
high reference value (set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value).
6-22 Terminal 54 Low Current
Range: Function:
4 mA
*
[0 - 20
mA]
Enter the low current value. This reference
signal corresponds to the low reference/
feedback value set in parameter 6-24 Terminal
54 Low Ref./Feedb. Value. To activate the live
zero timeout function in parameter 6-01 Live
Zero Timeout Function, set the value to >2 mA.
6-23 Terminal 54 High Current
Range: Function:
20 mA
*
[0 - 20
mA]
Enter the high current value corresponding
to the high reference/feedback value set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value.
6-24 Terminal 54 Low Ref./Feedb. Value
Range: Function:
0
*
[-4999 -
4999 ]
Enter the reference or feedback value that
corresponds to the voltage or current set in
parameter 6-21 Terminal 54 High Voltage/
parameter 6-22 Terminal 54 Low Current.
6-25 Terminal 54 High Ref./Feedb. Value
Range: Function:
Size
related
*
[-4999 -
4999 ]
Enter the reference or feedback value
that corresponds to the voltage or
current set in parameter 6-21 Terminal
54 High Voltage/
parameter 6-23 Terminal 54 High
Current.
6-26 Terminal 54 Filter Time Constant
Range: Function:
0.01 s
*
[0.01 - 10
s]
Enter the time constant, which is a rst-
order digital low-pass lter time constant
for suppressing electrical noise in terminal
54. A high time constant value improves
Parameters TR150 and TR170
56 02/2017 All rights reserved. BAS-SVP16B-EN