14-12 Function at Mains Imbalance
Option: Function:
When a severe mains imbalance is detected,
select 1 of the available functions.
[0]
*
Trip Trips the frequency converter.
[1] Warning Issues a warning.
[2] Disabled No action.
[3] Derate The frequency converter would derate.
3.10.3 14-2* Trip Reset
14-20 Reset Mode
Option: Function:
NOTICE
The motor may start without
warning. If the specied number of
automatic resets is reached within
10 minutes, the frequency
converter enters manual reset
mode. After the manual reset is
performed, the setting of
parameter 14-20 Reset Mode reverts
to the original selection. If the
number of automatic resets is not
reached within 10 minutes, or
when a manual reset is performed,
the internal automatic reset
counter returns to 0.
Note
Automatic reset is also active for
resetting Safe Torque O (STO) function.
Note
The setting in parameter 14-20 Reset
Mode is disregarded if re mode is
active (see parameter group 24-0*, Fire
Mode).
Select the reset function after tripping.
Once reset, the frequency converter can
be restarted.
[0]
*
Manual reset Select [0] Manual reset, to reset the
frequency converter via [Reset] or via
the digital inputs.
[1] Automatic reset x
1
Select [1]-[12] Automatic reset x 1…x20
to perform between 1 and 20 automatic
resets after tripping.
[2] Automatic reset x
2
[3] Automatic reset x
3
[4] Automatic reset x
4
14-20 Reset Mode
Option: Function:
[5] Automatic reset x
5
[6] Automatic reset x
6
[7] Automatic reset x
7
[8] Automatic reset x
8
[9] Automatic reset x
9
[10] Automatic reset x
10
[11] Automatic reset x
15
[12] Automatic reset x
20
[13] Innite auto reset Select [13] Innite Automatic Reset for
continuous resetting after tripping.
14-21 Automatic Restart Time
Range: Function:
10 s
*
[0 - 600
s]
To start the automatic reset function, enter the
time interval from trip. This parameter is active
when parameter 14-20 Reset Mode is set to [1] -
[13] Automatic reset.
14-22 Operation Mode
Option: Function:
To reset all parameter values to default, select
[2] initialisation.
[0]
*
Normal
operation
Select [0] Normal operation for normal
operation of the frequency converter with the
motor in the selected application.
[2] Initiali-
sation
Select [2] initialisation to reset all parameter
values to default settings, excluding bus
communication parameters, parameter groups
15-0* Operating Data and 15-3* Alarm Log. The
frequency converter is reset during the next
power-up.
Parameter 14-22 Operation Mode also reverts to
the default setting [0] Normal operation.
14-27 Action At Inverter Fault
Select how the frequency converter acts in the case of
overvoltage, overcurrent, short circuit, or grounding errors.
Option: Function:
[0] Trip
[1]
*
Warning
14-29 Service Code
Range: Function:
0
*
[0 - 0x7FFFFFFF ] Service use only.
Parameters TR150 and TR170