EasyManua.ls Logo

Trane TTK060K4 - Page 27

Trane TTK060K4
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SSC-PRC008-EN
27
System Performance Data
Cooling English Units
TTK042KD5 WITH MCX042GB5
AT 1200 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 37.6 27.0 29.3 31.6 33.7 35.0 2.56
85
65 40.6 22.3 24.7 26.9 29.3 31.5 2.67
67 42.2 19.9 22.2 24.5 26.8 29.1 2.72
71 45.3 14.9 17.2 19.4 21.8 24.1 2.83
61 36.6 26.6 28.8 31.2 33.1 35.0 2.78
95
65 39.4 21.9 24.1 26.5 28.7 31.1 2.89
67 40.9 19.4 21.7 24.0 26.3 28.6 2.95
71 44.0 14.5 16.7 19.1 21.3 23.7 3.07
61 35.1 25.6 27.9 30.0 31.9 33.7 3.03
105
65 37.9 21.0 23.3 25.6 27.8 30.1 3.14
67 39.4 18.6 20.8 23.1 25.4 27.7 3.20
71 42.2 15.9 16.0 18.2 20.5 22.8 3.33
61 33.6 24.9 27.1 29.1 31.0 32.6 3.28
115
65 36.2 20.2 22.5 24.8 27.1 29.3 3.40
67 37.6 17.8 20.2 22.3 24.7 26.9 3.46
71 40.5 12.9 15.2 17.4 19.7 22.0 3.59
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95
O
F
GROSS CAPACITY: 40.9 MBH
AIRFLOW: 1200 CFM
SYSTEM POWER: 3438 WATTS
NOM. SYSTEM AMPS: 8.5 AMPS
All temperature in Degree F

Related product manuals