SSC-PRC008-EN
43
System Performance Data
Cooling English Units
TTK042K4 WITH MCX042G1
AT 1200 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 39.9 28.7 31.2 33.5 35.8 37.2 3.74
85
65 43.1 23.7 26.2 28.6 31.1 33.5 3.89
67 44.7 21.1 23.6 26.1 28.4 30.9 3.96
71 48.1 15.8 18.3 20.7 23.2 25.6 4.13
61 38.8 28.3 30.6 33.1 35.2 37.2 4.05
95
65 41.8 23.3 25.7 28.2 30.5 33.0 4.22
67 43.4 20.6 23.1 25.5 28.0 30.4 4.30
71 46.7 15.4 17.8 20.3 22.6 25.2 4.47
61 37.2 27.2 29.6 31.9 33.9 35.8 4.42
105
65 40.2 22.3 24.7 27.2 29.6 32.0 4.59
67 41.8 19.7 22.1 24.6 27.0 29.4 4.67
71 44.8 16.9 17.0 19.3 21.8 24.2 4.86
61 35.6 26.4 28.8 31.0 33.0 34.7 4.78
115
65 38.5 21.5 24.0 26.3 28.8 31.1 4.97
67 39.9 18.9 21.4 23.7 26.2 28.6 5.05
71 42.9 13.7 16.1 18.5 21.0 23.4 5.23
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95
O
F
GROSS CAPACITY: 43.4 MBH
AIRFLOW: 1200 CFM
SYSTEM POWER: 4946 WATTS
NOM. SYSTEM AMPS: 8.8 AMPS
All temperature in Degree F