SSC-PRC008-EN
System Performance Data
Cooling English Units
TTK048K4 WITH MCX048G1
AT 1200 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 44.4 27.6 30.1 32.3 34.5 35.9 3.31
85
65 48.0 22.9 25.3 27.6 30.0 32.3 3.45
67 49.8 20.4 22.7 25.1 27.4 29.8 3.51
71 53.5 15.2 17.6 19.9 22.4 24.7 3.66
61 43.2 27.3 29.5 31.9 33.9 35.9 3.59
95
65 46.6 22.4 24.7 27.1 29.4 31.8 3.74
67 48.3 19.9 22.3 24.6 27.0 29.3 3.82
71 51.9 14.8 17.1 19.5 21.8 24.3 3.96
61 41.4 26.2 28.6 30.8 32.7 34.5 3.92
105
65 44.7 21.5 23.8 26.2 28.5 30.9 4.07
67 46.5 19.0 21.3 23.7 26.0 28.4 4.14
71 49.8 16.3 16.3 18.6 21.0 23.3 4.31
61 39.6 25.5 27.8 29.8 31.8 33.4 4.24
115
65 42.8 20.7 23.1 25.4 27.7 30.0 4.40
67 44.4 18.2 20.7 22.9 25.3 27.5 4.48
71 47.8 13.2 15.5 17.8 20.2 22.5 4.64
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95
O
F
GROSS CAPACITY: 48.3 MBH
AIRFLOW: 1200 CFM
SYSTEM POWER: 4420 WATTS
NOM. SYSTEM AMPS: 8.7 AMPS
All temperature in Degree F