Loading...
SSC-PRC008-EN
45
System Performance Data
Cooling English Units
TTK060K4 WITH MCX060G1
AT 1350 CFM
GROSS CAPACITY IN BTU/H x 1000
OUTDOOR I.D. GROSS SENS CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 kW
61 52.1 31.8 34.6 37.2 39.7 41.3 4.55
85
65 56.3 26.3 29.1 31.7 34.5 37.1 4.74
67 58.5 23.4 26.2 28.9 31.5 34.3 4.83
71 62.8 17.5 20.3 22.9 25.7 28.4 5.03
61 50.7 31.3 33.9 36.7 39.0 41.2 4.94
95
65 54.7 25.8 28.4 31.2 33.9 36.6 5.14
67 56.7 22.8 25.6 28.3 31.0 33.7 5.25
71 61.0 17.1 19.7 22.5 25.1 27.9 5.45
61 48.6 30.2 32.9 35.4 37.6 39.7 5.39
105
65 52.5 24.7 27.4 30.1 32.8 35.5 5.59
67 54.6 21.9 24.5 27.2 29.9 32.6 5.70
71 58.5 18.7 18.8 21.4 24.2 26.8 5.92
61 46.5 29.3 31.9 34.3 36.5 38.4 5.83
115
65 50.2 23.8 26.6 29.2 31.9 34.5 6.05
67 52.2 20.9 23.8 26.3 29.0 31.7 6.16
71 56.1 15.2 17.9 20.5 23.2 25.9 6.38
* Dry coil condition (Gross Capacity = Sensible Capacity)
Gross Capacity and Comp. kW are valid only for Wet Coil
Performance at the Rating Conditions of 80/67 & 95
O
F
GROSS CAPACITY: 56.7 MBH
AIRFLOW: 1350 CFM
SYSTEM POWER: 5850 WATTS
NOM. SYSTEM AMPS: 11.0 AMPS
All temperature in Degree F