RTWB Heat Pump Application
RLC-SVU02F-E442
Settings Menu
Access to each field within a mask using the "
Enter
" key. Change the field
value using the
Up
and
Down
keys and confirmation by "
Enter
".
1 = (0000 to 9999)
User Settings 1
1 = Front Panel Heat Setpoint (25.0°C..60.0°C: 35.0°C)
2 = Front Panel Cool Setpoint (-12.0°C..18.0°C: 6.0°C)
3 = Front Panel Heat/Cool switch (Heat, Cool)
4 = External Control (No, Partial, Full)
User Settings 2
1 = External Heat Setpoint Input Type (0-1V, 4-20mA)
2 = External Cool Setpoint Input Type (0-1V, 4-20mA)
Note: This screen is displayed if the External Control setting is "Full" (Mode