UHM-DHM-SF-1H 7
Service Facts
24V Variable Speed
System Status Setup Options [ ] = Current Setting
CMFRT CNT MODE
COMM [24VAC] 24VAC
* Unit specific
A/TUHMB060 3T [3T] 1.5T 2T 2.5T
COOLING CFM 2
COOLING CFM A/TUHMB080 3T [3T] 3.5T 2T 2.5T
* A/TUHMC100 4T [4T] 2.5T 3T 3.5T
A/TUHMD120 5T [5T] 3.5T 4T
CFM PER TON CFM PER TON A/TDHMB060 3T [3T] 1.5T 2T 2.5T
400 [ 400 ] 430 450 290 310 330 350 370 A/TDHMB080 3T [3T] 3.5T 2T 2.5T
A/TDHMC100 4T [4T] 2.5T 3T 3.5T
CLG STAGES CLG STAGES A/TDHMD120 5T [5T] 3.5T 4T
1 STG [1 STG] 2 STGS
** Unit specific
CLG 1ST STG CFM 3 CLG 1ST STG CFM 2
A/TUHMB060 960 [960] 1080 830 900
50% [50%] 55% 65% 80% A/TUHMB080 1400 [1400] 1610 1120 1260
A/TUHMC100 1620 [1620] 1790 1460 1540
CONT FAN CFM CONT FAN CFM A/TUHMD120 1890 [1890] 2000 1700 1790
50% [50%] 75% 100% 25% A/TDHMB060 1040 [1040] 1160 900 950
A/TDHMB080 1400 [1400] 1610 1300 1350
FAN PRERUN DLY FAN PRERUN DLY A/TDHMC100 1650 [1650] 1700 1500 1600
NONE [NONE] 1m@50% A/TDHMD120 1850 [1850] 2040 1660 1760
FAN SHRTRUN DLY FAN SHRTRUN DLY
NONE [NONE] 4m@80% 7.5m@80%
FAN OFF DLY FAN OFF DLY
1.5m@100% [1.5m@100%] NONE 1m@50% 2m@50% 3m@50%
HEAT CFM HEAT CFM
**
HT OFF DELAY HT OFF DELAY
100s [100s] 140 180 60
W1 W2 STG DLY W1 W2 STG DLY
00m [00m] 5m 10m 15m
FACTORY DEFLTS FACTORY DEFLTS
NO [NO] YES
EXIT EXIT
NO [NO] YES
NOTES:
3 This menu will only display when 2 STGS is chosen in previous menu.
2 Shown only when Communicating Outdoor Unit is not detected