Installation
27UNT-SVX10G-E4
Table 9 - Condensate pump performances (l/h)
Figure 18 - Multiple units drainage
A = To local drainage pipe
10 mm/m
> 22 mm i.d.
10 mm/m
10 mm/m
A
Discharge height -
H
Discharge length-L
Pump
manufacturer
5m 10m 20m 30m
Sauerman GP 1m 9.5 9.0 8.2 7.4
Sauerman GP 2m 7.0 6.5 5.7 4.9
Sauerman GP 3m 5.0 4.6 3.9 3.4
Sauerman GP 4m 4.0 3.6 3.1 2.8
Siccom ZN 1 m 10 9.5 87
Siccom ZN 2 m 9876
Siccom ZN 3 m 8765
Siccom ZN 4 m 6.5 544
UNT-SVX10G-BAT1_Mise en page 1 7/26/2013 2:41 PM Page 27