29UNT-SVX10G-E4
Installation
Table 10 - Minimum airflow (m3/h) in order to not damage heating elements - FCD
S
ize 101 103 203 204 304 306 406 408 508 512 612 721
500 W 100 100 80 80 80 80
7
50 W 150 120 120 120 120
1000 W 160 160 160 160
1500 W 240 240 240 190 190 265 265 375
2
000 W 320 320 250 250 350 350 500
3000 W 375 375 525 525 750
4
000 W 500 700 700 1000
Table 11 - Minimum airflow (m3/h) in order to not damage heating elements - FED
Unit size 100 200 300 400 500 600
5
00W 80 80 80
750W 120 120
1000W 160 160 160 160 160
1500W 240 240 240 240
2
000W 320 320 320 320
3
000W 480 480 480
The minimum airflow is ensured for the fan speed selection using the Trane selection tool.
CAUTION! Measure airflow above the minimum airflow in the above tables when selecting, on site, a lower speed than those
defined from the factory.
Heating capacityHeating capacity
UNT-SVX10G-BAT1_Mise en page 1 7/26/2013 2:41 PM Page 29