Startup
RT-SVX34F-EN 71
Table 47. Component static pressure drops Pa (SI) — 50 Hz
Nominal
Std Tons
(kW)
L/s
Std Air
Heating System Filters
Gas Heat Electric Heat ID Coil
Throw-
away
MERV 8 High
Eff.
MERV14
High Eff
Low High
1
Element
2
Element Dry Wet Adder 50 mm
100
mm 100 mm Economizer
80 (23)
3150 17 13 11 12 21 34 12 19 17 38 8
3540 21 16 14 15 26 41 17 26 24 45 10
3930 26 20 17 19 30 48 19 31 29 50 12
4320 31 24 21 23 36 55 22 36 34 57 15
4720 37 29 25 27 41 62 26 43 38 65 17
88 (25)
3540 21 16 14 15 26 41 17 26 24 45 10
3930 26 20 17 19 30 48 19 31 29 50 12
4320 31 24 21 23 36 55 22 36 34 57 15
5120 44 34 29 32 41 62 26 43 41 67 17
103 (29)
4130 29 22 19 21 44 68 22 36 31 55 13
4520 34 27 23 25 51 78 24 41 38 62 16
4920 41 32 27 29 66 97 29 50 46 77 19
5310 47 37 32 34 75 109 31 53 50 86 23
118 (33)
4720 2 7 18 27 43 67 26 43 38 65 17
5120 3 8 21 32 49 75 29 50 43 69 19
5510 3 10 24 37 56 84 31 55 48 77 21
5900 4 11 27 42 62 92 34 62 55 84 24
6290 4 12 31 48 69 101 36 67 60 88 27
6680 5 14 35 54 77 111 41 77 67 98 30
146 (42)
5900 4 11 27 42 78 115 34 62 55 84 24
6290 4 12 31 48 86 126 36 67 60 88 27
6680 5 14 35 54 96 139 41 82 72 100 30
7070 5 16 39 60 115 162 46 91 82 112 34
7470 6 18 44 67 126 176 48 98 86 124 39
Note: Static pressure drops of accessory components must be added to external static pressure to enter fan performance tables.