12
Table 6 Torque Specifications (Unless Otherwise Labeled)
A. Nut and Bolt Combinations
Bolt Shaft Size
Grade 2
Standard
Electrical Connections with Belleville
Washers
lb-in
N-m
lb-in
N-m
1/4
53
6.0
46
5.2
5/16
107
12.1
60
6.8
3/8
192
21.7
95
10.7
1/2
528
60.0
256
28.9
B. Main Input Circuit Breaker
Breaker Size
Wire
Size
Compression Lug
lb-in
N-m
Up to 110 Amp
#14 - #10
#8 - #3
#2 - #3/0
35
100
150
4.0
11.4
17.1
C. Branch Circuit Breakers
lb-in
N-m
Up to 30 Amp
35
4.0
40 to 100 Amp
45
5.1
D. Terminal Block Compression Lug
AWG Wire Size or Range
lb-in
N-m
#14 - #10
35
4.0
#8
40
4.5
#6 - #00
120
13.6
AWG #2 Main RPDU lugs
45-50