7
Operation
Description Address Value 0 Value 1
Reserved 0x0117
Alarm Rectifier Main Fail 0x0118 OK Rectifier Main Fail
Alarm Rectifier Hi DC Stop 0x0119 OK Rectifier Hi DC Stop
Alarm Over Temp or Fuse Fail 0x011A OK Over Temp or Fuse Fail
Alarm Battery Low 0x011B OK Battery Low
Alarm Battery Low Stop 0x011C OK Battery Low Stop
Alarm Battery Ground Fault 0x011D OK Battery Ground Fault
Inverter On 0x011E Inverter Off Inverter ON
Alarm Inverter Overload 0x011F OK Inverter Overload
Alarm Inverter Abnormal 0x0120 OK Inverter Abnormal
Alarm Load on Reserve 0x0121 Load Not On Reserve Load on Reserve
Alarm Reserve Mains Fail 0x0122 OK Reserve Mains Fail
Alarm Reserve Freq. Abnormal 0x0123 OK Reserve Freq. Abnormal
Alarm Test In Progress 0x0124 No Test In Progress Test In Progress
Alarm Test Error 0x0125 No Test Error Test Error
UPS In Sleep Mode 0x0126 UPS Not In Sleep Mode UPS In Sleep Mode
Reserved 0x0127
Alarm Bypass Volt/Freq Bad 0x0128 OK Bypass Volt/Freq Bad
Alarm Bypass Phase Sequence Bad 0x0129 OK Bypass Phase Sequence Bad
Alarm Bypass STS Overload 0x012A OK Bypass STS Overload
Alarm Bypass STS Over 0x012B OK Bypass STS Over
Alarm Bypass STS Fault 0x012C OK Bypass STS Fault
Reserved 0x012D
Reserved 0x012E
Reserved 0x012F
Note: Your UPS may not support all fields.
Coils (Range 0x0200 - 0x020F, Read Function 0x01, Write Function 0x05)
The Read Coils function reads 1-2000 contiguous status of coils in a remote device. The starting address and number of coils
is specified by the request Protocol Data Unit. Addresses start at 0 and Coils numbered 1-16 would address as 0-15.
The Write Coils function writes a single output to ON/OFF in a remote device. A specified constant in the data field requests the
ON/OFF state. Addresses start at 0 and Coils numbered 1 would address as 0.
Description Address Value 0 Value 1
UPS Buzzer 0x0200 Silence Alarm
Shutdown Type 0x0201 UPS Output UPS System
Economy Mode Setting 0x0202 Disable Enable
ATX PC Reboot Function 0x0203 Disable Enable
AC Fail & Restore Auto-Reboot 0x0204 Disable Enable
ATX PC Resume Function 0x0205 Disable Enable
Enable/Disable Inverter 0x0206 Disable Enable
EPO Setting 0x0207 Disable Enable
Enable/Disable Inverter 0x0208 Disable Enable
Clear SRAM 0x0209 Clear SRAM Clear SRAM
Cancel Shutdown Restart 0x020A Cancel Shutdown Restart Cancel Shutdown Restart
Set Output On/Off 0x020B OFF ON
Reserved 0x020C
Reserved 0x020D
Reserved 0x020E
Reserved 0x020F
Note: Your UPS may not support all fields.