The test must be conducted by a technician
The gas hose and gas cylinder must be connected.
Turn off all consumers.
Open stop valves and, if present, the gas remote switch.
Press in the triggering element of the crash sensor (9) sufficiently
far that the yellow reset button(7) comes out so that the crash sen-
sor is in the “not ready for operation” position (figure 2b).
Remove the screw cap (10) from the test connection and connect
the test pump with test hose to the test connection.
10
7
9
Figure 3: MonoControl CS
Check for leaks (e.g in Germany in accordance with G 607).