26 EN
Checking for leaks in the high-pressure section
The screw joints of the high-pressure hose at the gas cylinder valve
and on the gas filter / MonoControl must be checked for leaks, us-
ing suitable means such as a leak-finder spray in accordance with
EN14291. The operator is responsible for this.
Checking for leaks in the low-pressure section
(maximum test pressure 150 mbar)
The test must be conducted by a technician
The gas hose and gas cylinder must be connected.
Turn off all consumers.
Open stop valves and, if present, the gas remote switch.
Use the Torx T20(10) from the screw aid(9) to turn the reset button
clockwise to the “not ready for operation” position.
Remove the screw cap (8) from the test connection and connect
the test pump with test hose to the test connection.