The MIN CFM ALM item sets the duct’s flow alarm set point. A 
minimum flow alarm is defined as when the duct flow is less 
than the MIN CFM ALM set point. 
 
The 2 LOW ALM item sets the second sensor’s low alarm set 
point. A low alarm condition is defined as when the magnitude 
of the second sensor’s room pressure falls below or goes in the 
opposite direction of the 2 LOW ALM set point. The alarm can 
be a negative or positive pressure alarm set point. 
 
The second sensor low and high alarms must be programmed 
for the same pressure direction; positive or negative. In 
addition, the PresSura controller has a minimum dead band of 
40 ft/min between the second sensor low and high alarms. The 
dead band helps prevent nuisance alarms. 
 
The second sensor monitors the room pressure of a second 
space (typically an ante room), and is not part of the primary 
sensor or control sequence. This alarm is on when the DIM is in 
positive or negative mode. 
 
This item is enabled when the second pressure sensor item is 
enabled (see menu item 2 SENSOR).