The 2 HIGH ALM item sets the second sensor’s high alarm set 
point. A high alarm condition is defined as when the magnitude 
of the second sensor’s room pressure rises above the 2 HIGH 
ALM set point. The alarm can be a negative or positive 
pressure alarm set point. 
 
The second sensor low and high alarms must be programmed 
for the same pressure direction; positive or negative. In 
addition, the PresSura controller has a minimum dead band of 
40 ft/min between the second sensor low and high alarms. The 
dead band helps prevent nuisance alarms. 
 
The second sensor monitors the room pressure of a second 
space (typically and ante room), and is not part of the primary 
sensor or control sequence. This alarm is on when the DIM is in 
positive or negative mode. 
 
This item is enabled when the second pressure sensor item is 
enabled    (see menu item 2 SENSOR). 
The ALARM RESET item selects how the alarms terminate 
after the unit returns to the safe pressure range (pressure or 
flow). UNLATCHED (alarm follow) automatically resets the 
alarms when the unit reaches the safe pressure range. 
LATCHED requires the staff to press the RESET key after the 
unit returns to safe pressure range. The ALARM RESET affects 
the audible alarm, visual alarm, and relay output, which means 
all are latched or unlatched. 
 
The AUDIBLE ALM item selects whether the audible alarm is 
turned ON or OFF. Selecting ON requires the staff to press the 
MUTE key to silence the audible alarm. Selecting OFF 
permanently mutes all audible alarms.