TBEN-LG EtherNet/IP
TM
Configuration Guide
TURCK • 3000 Campus Drive • Minneapolis, MN 55441-2656 10
Phone: 763.553.7300 • Toll Free: 800.544.7769 • Fax: 763.553.0708 • www.turck.us
Device Type
M12, d-coded
M12, a-coded
M12, a-coded
Power (7/8“)
TBEN-LG-16DXP
P1 P2
1 = TD+ 1 = RD+
2 = RD+ 2 = TD+
3 = TD- 3 = RD-
4 = RD- 4 = TD-
(see „Note 1“)
C0 … C7
1 = VAUX1 (+)
2 = Second input
3 = V1 (-)
4 = First input
5 = FE
DXP allows for any
combination of IO per
single connector
C0 … C7
1 = VAUX2 (+)
2 = Second output
3 = V2 (-)
4 = First output
5 = FE
Note 1:
The pin-out of P1 and P2 are “crossed over”. P1 has a “NIC-Type” connection and P2 has a “Switch-
Type” connection. The TBEN devices are configured with Auto-MDIX enabled when not used for fast
startup / quick connect. In that case the switch detects the cabling type itself.
With the crossed connection of P2 it is possible to connect multiple devices in a row without Auto-MDIX
with 1:1 EtherNet cables. This ensures that the switch could establish a link quickly for fast start-up devic-
es.
Note 2:
VAUX1 = V1 – 0.2 VDC (voltage drop over protective circuit)
VAUX2 = V2 – 0.2 VDC (voltage drop over protective circuit)