TBEN-LG EtherNet/IP
TM
Configuration Guide
TURCK • 3000 Campus Drive • Minneapolis, MN 55441-2656 19
Phone: 763.553.7300 • Toll Free: 800.544.7769 • Fax: 763.553.0708 • www.turck.us
Setting up IP Address
TBEN has three rotary switches which are used to set either the last octet of the device IP ad-
dress or device mode of operation. Valid address range and mode of operation are:
The address switches are pre-set out of box to 600 (PGM-DHCP mode). IP address can be as-
signed immediately using DHCP server.
General procedure for IP address setup is:
− Set rotary switches to desired mode (300, 400, 500, 600)
− Cycle power to the station
− Run IP address utility to assign IP address
− Set address switches to static rotary position or PGM mode
− Cycle power to the station
The TBEN station IP address can be configured and/or changed in following ways:
− Using static rotary mode
− BootP Server utility
− DHCP Server utility
− TBEN Web page
− IP Address tool
Address Switches in Static Rotary
When address switches are in static mode, the last octet may be dialed in 1-254 range.
Addresses 0 and 255 are reserved and cannot be used.
Following example shows the last octet set to of address xx.xxx.xxx.173
Setting rotary switches to any other position not listed on the device or data sheet sets device
into DHCP mode and bus LED flashes green / red.