PGM-DHCP Mode (600)
When rotary switches are set to 600, it enables PGM–DHCP mode of operation. It is the default,
out-of-box setup mode of the device. To assign IP address the first time:
− Power up the device
− Run the DHCP utility and assign IP address
− Disable the DHCP request from the module by clicking the Disable BOOTP/DHCP but-
ton in the utility
− Leave the rotary switches in 600 (PGM-DHCP) position or set switches to a number that
matches the last octet of the assigned IP address [1,…,254]
− Power cycle the device
Note:
When the device is set to 600 (PGM-DHCP) mode, its IP address can be further
changed using either the IP Address Tool or WEB page.