TBEN-LG EtherNet/IP
TM
Configuration Guide
TURCK • 3000 Campus Drive • Minneapolis, MN 55441-2656 27
Phone: 763.553.7300 • Toll Free: 800.544.7769 • Fax: 763.553.0708 • www.turck.us
Restore Mode (0)
When rotary switches are set to 0 and device power cycled, the device recovers only IP address
to factory default value:
− IP address: 192.168.1.254
− Mask: 255.255.255.0
− Gateway: 192.168.1.1
The device responds to PING command, but it does not operate when switches are set to 0. At
this point it is necessary either, to assign new IP using address tools as described earlier, or
simply dial rotary switches between xx=1,…, 253; to set address as 192.168.1.x.
Factory Reset Mode (900)
The device resets itself to factory default settings, as follows:
− Set the rotary switches to 900 position
− Power up the device (the BUS LED solid red) and wait 10 sec
− Set the rotary switches to 600 (PGM-DHCP mode)
− Cycle power to the device