Note:  Do not attempt to compen-
sate for insufficient adjustment in the 
escutcheon plate by under or over-
tightening the nozzle. Re-adjust the 
position of the nozzle fitting to suit.
Absence of an escutcheon, which is 
used to cover a clearance hole, can 
delay the time to nozzle operation in a 
fire situation.
Care and 
Maintenance
The TYCO Type ULF AM22 AQUAMIST 
Nozzles must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system 
main control valve for maintenance 
work on the fire protection system 
that it controls, obtain permission to 
shut down the affected fire protection 
system from the proper authorities 
and notify all personnel who may be 
affected by this action.
Nozzles which are found to be leaking 
or exhibiting visible signs of corrosion 
must be replaced.
Automatic nozzles must never be 
painted, plated, coated, or other-
wise altered after leaving the factory. 
Modified nozzles must be replaced. 
Nozzles that have been exposed to 
corrosive products of combustion, but 
have not operated, should be replaced 
if they cannot be completely cleaned 
by wiping the nozzle with a cloth or by 
brushing it with a soft bristle brush.
Care must be exercised to avoid 
damage to the nozzles - before, during, 
and after installation. Nozzles damaged 
by dropping, striking, wrench twist/
slippage, or the like, must be replaced. 
Also, replace any nozzle that has a 
cracked bulb or that has lost liquid from 
its bulb. (Ref. Installation Section.)
Frequent visual inspections are recom-
mended to be initially performed for 
nozzles installed in potentially corro-
sive atmospheres to verify the integ-
rity of the materials of construction 
and finish as they may be affected by 
the corrosive conditions present for a 
given installation. Thereafter, annual 
inspections per applicable standards 
are required, in addition to inspec-
tions required by the authority having 
jurisdiction.
The owner is responsible for the 
inspection, testing, and maintenance of 
their fire protection system and devices 
in compliance with this document, as 
well as with the applicable standards 
of the NATIONAL FIRE PROTECTION 
ASSOCIATION (e.g., NFPA 20, 25, and 
750), in addition to the standards of 
any other authorities having jurisdic-
tion. Contact the installing contrac-
tor or product manufacturer with any 
questions.
Water-mist fixed systems should be 
inspected, tested, and maintained by 
a qualified Inspection Service in accor-
dance with local requirements and/or 
national codes.
Limited  
Warranty
For warranty terms and conditions, visit 
www.tyco-fire.com.
Ordering  
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate 
the full product name and Part Number 
(P/N.)
Type ULF AM22 AQUAMIST Nozzles
Specify: Type ULF AM22 AQUAMIST 
Nozzle with (specify finish), tempera-
ture rating (specify), P/N (specify):
Natural Brass
57°C (135°F) ..................49-209 -1-135
68°C (155°F) ..................49-209 -1-155
79°C (175°F ) ..................49-209-1-175
93°C (200°F)..................49-209-1-200
Chrome Plated
57°C (135°F) ..................49-209-9-135
68°C (155°F) ..................49-209-9-155
79°C (175°F ) ..................49-209-9-175
93°C (200°F)................. 49-209-9-200
Signal White* (RAL9003)
57°C (135°F) ..................49-209-4-135
68°C (155°F) ..................49-209-4-155
79°C (175°F ) ..................49-209-4-175
93°C (200°F)..................49-209-4-200
Pure White** (RAL9010)
57°C (135°F) ..................49-209-3-135
68°C (155°F) ..................49-209-3-155
79°C (175°F ) ..................49-209-3-175
93°C (200°F)..................49-209-3-200
* Previously known as Bright White
** Eastern Hemisphere sales only
Nozzle Wrench
Specify: W-Type 6 Nozzle Wrench, 
P/N 56-000-6-387
Escutcheon
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
*Refer to Technical Data Sheet TFP770
Temperature  
Rating
Bulb Fluid 
Color
57°C (135°F) Orange
68°C (155°F) Red
79°C (175°F) Yellow
93°C (200°F) Green
Orice
Insert
Diffuser
Ejection
Spring
Bulb
Loading
Screw
Button
Frame
Sealing
Assembly
Strainer
Components:
-
-
-
-
-
-
-
-
-
2
9
8
6
7
4
5
3
1
DIFFUSER
SHAPE
WRENCH
FLATS
ESCUTCHEON
PLATE SEATING
SURFACE
1/2"
NPT
9
8
7
6
4
5
3
1
2
11,1 mm
(7/16")
NOMINAL
MAKE-IN
17,5 mm
(11/16")
17,5 mm
(11/16")
41,3 mm
(1-5/8")
31,0 mm
(1.22")
58,7 mm
(2-5/16")
(USE ONLY
END "A")
FIGURE 1 
TYPE ULF AM22 AQUAMIST NOZZLE 
NOMINAL DIMENSIONS
TABLE A 
TEMPER ATURE R ATING 
SELECTION
FIGURE 2 
W-TYPE 6 NOZZLE WRENCH