Only wet pipe systems may be utilized for installation.
Minimum required flow rate based on coverage areas and temperature ratings.
Sprinkler locations must comply with NFPA 13 obstruction rules.
Sprinklers are installed relative to the ceiling mounting surface.
Details minimum and maximum spacing requirements between sprinklers.
Only wet pipe systems may be utilized for installation.
Minimum required flow rate based on coverage areas and temperature ratings.
Sprinkler locations must comply with NFPA 13 obstruction rules.
Sprinklers are installed relative to the ceiling mounting surface.
Details minimum and maximum spacing requirements between sprinklers.
The Tyco Series LFII (TY2596) Residential Concealed Pendent Sprinklers are decorative, fast-response, fusible solder sprinklers designed for use in residential occupancies such as homes, apartments, dormitories, and hotels. These sprinklers are UL and C-UL Listed, and NYC Approved under MEA 44-03-E.
The Series LFII (TY2596) sprinklers are designed to activate in response to heat from a fire. The cover plate assembly conceals the sprinkler's operating components above the ceiling, providing an aesthetically pleasing, flat profile. When exposed to heat, the cover plate, normally soldered to the support cup at three points, falls away to expose the sprinkler assembly. At this point, the deflector, supported by the arms, drops down to its operated position. The fusible link of the sprinkler assembly, comprised of two link halves soldered together with a thin layer of solder, melts when the rated temperature is reached. This causes the link halves to separate, allowing the sprinkler to activate and flow water. The design incorporates heat sensitivity and water distribution characteristics proven to help control residential fires and improve the chance for occupants to escape or be evacuated.
The Series LFII sprinklers are intended for use in wet pipe residential sprinkler systems. They are suitable for:
The sprinklers are shipped with a Disposable Protective Cap. This cap serves multiple purposes:
The Series LFII (TY2596) sprinklers must be maintained and serviced in accordance with the provided instructions and applicable standards of the National Fire Protection Association (e.g., NFPA 25).