Models BB, SD, HIP, and AP 
Specific Application Sprinklers
For Protecting Attics
Page 1 of 28  AUGUST 2014  TFP610
IMPORTANT
Always refer to Technical Data 
Sheet TFP700 for the “INSTALLER  
WARNING” that provides cau-
tions with respect to handling 
and installation of sprinkler sys-
tems and components. Improp-
er handling and installation can 
permanently damage a sprin-
kler system or its components 
and cause the sprinkler to fail  
to operate in a fire situation or cause  
it to operate prematurely.
General 
Description
The TYCO Model BB (Back to Back), 
SD (Single Directional), HIP, and AP 
(Attic Plus) Specific Application Sprin-
klers for Protecting Attics are fire 
sprinklers for combustible and non-
combustible sloped attic spaces. The 
Model BB, SD, and HIP are Specific 
Application Attic Sprinklers, whereas 
the Model AP is a Specific Applica-
tion Combustible Concealed Space 
Sprinkler having specific applica-
tion criteria for its use with the Mod-
els BB, SD, and HIP in attic spaces. 
Specific Application Attic Sprinklers 
provide superior fire protection in attic 
spaces, and when compared to Stan-
dard Spray Sprinklers, cost savings 
are achieved by eliminating branch-
line materials and the associated in-
stallation labor. The Specific Applica-
tion Sprinklers for Protecting Attics 
have undergone the most extensive 
fire testing ever performed for sloped 
attic spaces. They are UL Listed with 
their specific application guidelines for 
use as special sprinklers as defined by 
the National Fire Protection Associa-
tion (NFPA).
The Specific Application Attic Sprin-
klers provide an extended coverage 
spacing alternative to the restricted 
spacing of Standard Spray Sprinklers. 
The restricted spacings of Standard 
Spray Sprinklers used within attics is 
described in the 2007 edition of NFPA 
13, Table 8.6.2.2.1(a) and Section 
8.6.4.1.4.
The Specific Application Attic Sprin-
klers are the first sprinklers to be:
•  Listed for extended coverage in 
combustible construction
•  Full-scale fire tested in both wet and 
dry system scenarios
•  Full-scale tested for use in wood 
truss construction
•  Listed for specific roof slopes (Ref. 
Table A)
The Specific Application Attic Sprin-
klers provide the best level of pro-
tection, and control cost by eliminat-
ing the need for additional sprinklers 
and branchline piping. In many cas-
es, an attic can be entirely protected 
with just one line of piping located be-
low the peak of the roof using Model 
BB (Back to Back) Sprinklers. If there 
is a need for Model SD (Single Direc-
tional) or Model HIP Sprinklers, one 
line of either of these sprinkler types 
is sufficient at each area being cov-
ered. For example and assuming the 
use of Standard Spray Sprinklers, a 
system in a 60 foot (18,3 m) wide attic, 
with up to a 12:12 roof pitch, designed 
to the 2007 edition of NFPA 13, would 
require seven branchlines to cover the 
main portion of the attic and several 
additional branchlines to cover the hip 
areas. With the Specific Application 
Attic Sprinklers, the required coverage 
can be obtained with just one branch-
line running below the peak and one 
down each slope of the hip beam. This 
would result in approximately 90% 
less pipe needed for installation. This 
reduction in the number of branch-
lines saves the cost of the pipe, fit-
tings, hangers, and associated labor 
by eliminating up to five branchlines.
Another important aspect of the Spe-
cific Application Attic Sprinkler tech-
nology is the reduction in system 
volume. This volume reduction may 
result in reducing the size of a dry 
pipe valve (and air compressor) and 
possibly allow for quicker water deliv-
ery times, eliminating the need for an 
accelerator.