General
Description
The Tyco
®
RAVEN™ Institutional Pen-
dent and Horizontal Sidewall Sprin-
klers are quick response spray sprin-
klers designed for use in areas such
as correctional, detention, and mental
health care facilities, as well as other
commercial buildings. Both the pen-
dent and horizontal sidewall styles
are available for standard or extended
coverage applications.
Features:
The RAVEN assembly increases •
the difficulty of tampering with the
sprinkler that may cause a false
activation.
The tamper resistant nature of the •
RAVEN helps reduce the opportu-
nity for individuals to injure them-
selves or others with components of
a fire sprinkler.
The RAVEN optimizes an aestheti-•
cally appealing ush design that
conceals all of the operating parts.
NOTICE
The RAVEN Institutional Sprinklers
described herein must be installed
and maintained in compliance with
this document and with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any authorities having ju-
risdiction. Failure to do so may impair
the performance of these devices.
Tyco Fire Suppression & Building
Products specifically disclaims any li-
ability for damages or injury (includ-
ing death) arising out of or caused by
manipulation, dismantling, or misuse
of RAVEN Sprinklers or the use or at-
tempted use of the RAVEN Sprinklers
or any component thereof as an instru-
ment unrelated to its intended function
as a fire protection device.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or manufac-
turer should be contacted with any
questions.
Sprinkler
Identification
Numbers
SIN DOT
COLOR*
APPLICATION
TY3281 Black Pendent Standard
Coverage
TY3282 Green Pendent Extended
Coverage
TY3381 Red HSW Standard
Coverage
TY3382 Purple HSW Extended
Coverage
Refer to Figures 1 through 4 for SIN Color *
Dot location.
Technical
Data
Approvals:
UL and C-UL Listed.
(Refer to the Design Criteria section.)
Maximum Working Pressure:
175 psi (12,1 bar)
Inlet Thread Connection:
1/2 inch NPT
Discharge Coefficient:
K=5.6 GPM/psi
1/2
(80,6 LPM/bar
1/2
)
Temperature Rating:
165°F/ 74°C
Finishes:
Sprinkler: Chrome or White
Escutcheon: Chrome or White
Physical Characteristics:
Body .....................Brass
Deflector Assembly .........Bronze
Sealing Assembly ................
. . . . . . . . . .Beryllium Nickel w/Teflon*
Link Assembly .............Copper
Patents:
Patent pending
RAVEN™ Institutional — 5.6 K-factor
Pendent and Horizontal Sidewall Sprinklers
Quick Response, Standard and Extended Coverage
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Page 1 of 10 APRIL, 2009 TFP651
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Question and Answer IconNeed help?

Do you have a question about the Tyco RAVEN Institutional TY3281 and is the answer not in the manual?

Tyco RAVEN Institutional TY3281 Specifications

General IconGeneral
ManufacturerTyco
CategoryIrrigation System
MaterialBrass
Product LineRAVEN
Connection Size1/2 inch
ModelRAVEN Institutional TY3281

Summary

General Description

Key Features

Highlights tamper-resistance, flush aesthetics, and safety aspects of the sprinkler design.

Important Notices

Covers compliance with standards, liability disclaimers, and critical handling/installation warnings.

Sprinkler Identification and Specifications

Identification Mapping

Correlates SIN numbers, DOT Color, and Application types for different sprinkler models.

Technical Specifications

Details approvals, maximum working pressure, temperature rating, finishes, and physical characteristics.

Design Criteria

Standard Coverage Installation

Installation requirements for standard coverage pendent (TY3281) and sidewall (TY3381) sprinklers.

Extended Coverage Installation

Installation requirements for extended coverage pendent (TY3282) and sidewall (TY3382) sprinklers.

General Installation Requirements

Covers escutcheon options, spacer usage for adjustment, and maintaining tamper resistance.

Operation Overview

Installation Procedures

Pendent Sprinkler Installation

Step-by-step instructions for correctly installing the RAVEN pendent sprinklers.

Horizontal Sidewall Sprinkler Installation

Step-by-step instructions for correctly installing the RAVEN horizontal sidewall sprinklers.

Care and Maintenance

Inspection Protocol

Guidelines for regular inspection of sprinklers to detect damage or tampering.

Maintenance Obligations

Outlines owner's responsibility and the need for qualified service for fire protection systems.

Product Information

Limited Warranty

Details the ten-year warranty against defects in material and workmanship.

Disclaimer of Liability

States liability limitations for damages arising from sprinkler misuse or alteration.

Ordering Guide

Instructions for specifying and ordering different sprinkler models, escutcheons, and accessories.