CONCEALED PENDENT SPRINKLER with 1/2" ADJUSTMENT
MODEL F690 DESIGNER
QUICK RESPONSE, 3 mm BULB TYPE, 1/2" ORIFICE, 1/2" NPT
GENERAL DESCRIPTION
The 1/2 inch (15 mm) orifice Model
F690 Designer, Quick Response Con-
cealed Pendent Sprinklers (Ref.Figure
A) are pendent automatic sprinklers of
the frangible bulb type.They are “quick
response - standard orifice spray
sprinklers” intended for use in fire
sprinkler systems designed in accord-
ance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g. UL
Listing is based on NFPA 13 require-
ments). The F690 produces a hemi-
spherical water distribution pattern be-
low the deflector. Each unit includes a
Cover Plate Assembly which conceals
the sprinkler operating components
above the ceiling.
The small Cover Plate is flat with a low
profile which blends in with the ceiling
for an aesthetically pleasing appear-
ance. Standard finishes for the Cover
Plate are satin chrome plated and
painted white. Other factory applied
painted finishes for the Cover Plate are
available on special order.
The separable two-piece design of the
Cover Plate and Mounting Cup As-
semblies allows installation of the
sprinklers and pressure testing of the
fire protection system prior to installa-
tion of a suspended ceiling or applica-
tion of the finish coating to a fixed
ceiling.The separable design also per-
mits removal of suspended ceiling
panels for access to building service
equipment, without having to first shut
down the fire protection system and
remove sprinklers.
Also, the separable two-piece design
of the the F690 Concealed Sprinkler
provides for 1/2 inch of vertical adjust-
ment, to reduce the accuracy to which
the length of fixed pipe drops to the
sprinklers must be cut.
Each sprinkler is shipped with a dam-
age resistant Protective Cap, which
can be temporarily left in place until
installation of the ceiling is complete.
APPROVALS AND STANDARDS
The 1/2 inch orifice Model F690 Quick
Response Concealed Pendent Sprin-
klers are listed by Underwriters Labo-
ratories Inc.and listed by Underwriters
Laboratories Inc. for use in Canada
(i.e., C-UL Listed).
The Model F690 Sprinklers are ap-
proved by Factory Mutual Research
Corporation as standard response
sprinklers for use in Hazard Occupan-
cies up to and including Ordinary,
Group II. The Ordinary Hazard Occu-
pancy approval is limited to use in wet
pipe systems and preaction systems
qualifying as wet pipe systems.
The laboratory listings apply to the
temperature ratings and Cover Plate
finishes indicated in Figure A.
WARNING
The ModelF690 QuickResponse Con-
cealed Pendent Sprinklers described
herein must be installed and main-
Printed in U.S.A. 6-98
TD578Q
TEMPERATURE RATINGS:
135°F / 57°C
155°F / 68°C
175°F / 79°C
200°F / 93°C
K-FACTOR (NOMINAL):
5.6 ( GPM ÷ psi
1/2
)
80.6 ( LPM ÷ bar
1/2
)
ADJUSTMENT:
1/2 INCH (12.7mm)
COVER PLATE FINISHES:
CHROME PLATED
WHITE PAINTED
SPECIAL COLOR PAINTED
Dim. Inches MM
A- 3-5/16 84,1
B- 3/16 4,8
C- 2-5/8 66,8
D-Min. 1-13/16 46,0
D-Nom. 2-1/16 52,4
D-Max. 2-5/16 58,7
FIGURE A
MODEL F692 QUICK RESPONSE CONCEALED PENDENT SPRINKLER