Page 1 of 8  MARCH 2023  TFP633
Worldwide 
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet 
TFP2300 for warnings pertaining to 
regulatory and health information.
Always refer to Technical Data 
Sheet TFP700 for the “INSTALLER  
WARNING” that provides cautions 
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and 
installation can permanently damage 
a sprinkler system or its compo-
nents and cause the sprinkler to fail  
to operate in a fire situation or cause  
it to operate prematurely.
Scan the QR code or enter the URL 
in a web browser to access the most 
up-to-date electronic version of this 
document. Data rates may apply.
docs.jci.com/tycore/tfp633
Model CC3 — 4.2 and 5.6 K-factor 
Combustible Concealed Space Sprinklers 
Specic Application, Upright
General 
Description
The Model CC3 Combustible Con-
cealed Sprinklers are quick response, 
upright, specic application sprinklers 
designed to provide protection of spe-
cic light hazard combustible, as well 
as non-combustible, con cealed spaces 
requiring sprinkler protection. The 
Model CC3 Sprinklers comply with the 
criteria for the protection of combus-
tible concealed spaces as described 
in NFPA 13.
The Model CC3 Sprinklers are 
designed for installation on BLAZE-
MASTER CPVC wet pipe systems, 
other UL Listed CPVC pipe products, 
Technical 
Data
Approvals
UL Listed
(Listings and approvals only apply to the 
service conditions indicated in the Design 
Criteria sections.)
Antifreeze Compatibility
Model CC3 TY2199 4.2K and TY3199 5.6K 
Sprinklers can be used with:
•  LFP
®
 Antifreeze in accordance with 
Technical Data Sheet TFP1680, LFP
®
 
Antifreeze Agency Listed Solution for Fire 
Sprinkler Systems
•  LFP
®
 Antifreeze+ in accordance with 
Technical Data Sheet TFP1682, LFP
® 
Antifreeze+ Agency Listed Solution for 
Fire Sprinkler Systems
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
½ in. NPT
Discharge Coefficient
K = 4.2 GPM/psi
½
 (60,5 LPM/bar
½
) 
K = 5.6 GPM/psi
½
 (80,6 LPM/bar
½
)
Temperature Rating
200°F (93°C)
Finish
Natural Brass
Physical Characteristics
Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb .........................Glass (3 mm)
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Deector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
and steel wet pipe or dry pipe sprinkler 
systems (see the respective Design Cri-
teria sections). The Model CC3 Sprin-
klers are designed to be installed in the 
following arrangements for both wet 
CPVC and steel:
•  4.2K
14 ft (4,3 m) maximum between 
sprinklers
196 ft²
 
(18,2 m²) maximum coverage 
area
•  5.6K
16 ft (4,9 m) maximum between 
sprinklers
256 ft²
 
(23,8 m²) maximum coverage 
area
•  6 in. (152,4 mm) minimum height for 
joist with steel pipe or CPVC when 
insulation lled. 12 in. (305 mm) min-
imum height for all other arrange-
ments and sizes
•  60 in. (1524 mm) maximum height 
from joist to joist and 84 in. 
(2134 mm) from oor to ceiling
•  60 in. (1524 mm) maximum height for 
truss and bar joist
NOTICE
The Model CC3 Combustible Con-
cealed Sprinklers described herein 
must be installed and maintained in 
compliance with this document, as 
well as with the applicable standards 
of the NATIONAL FIRE PROTECTION 
ASSOCIATION (NFPA), in addition to 
the standards of any other authorities 
having jurisdiction. Failure to do so 
may impair the performance of these 
devices.
The owner is responsible for main-
taining their fire protection system 
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any 
questions.
Sprinkler 
Identication 
Number
TY2199 – Upright, 4.2K
TY3199 – Upright, 5.6K