Model SW-20 and SW-24 — 11.2 K-factor 
Extended Coverage Ordinary Hazard 
Horizontal Sidewall Sprinklers (Standard Response)
Page 1 of 6  MARCH 2014  TFP230
IMPORTANT
Always refer to Technical Data 
Sheet TFP700 for the “INSTALLER  
WARNING” that provides cautions 
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage 
a sprinkler system or its compo-
nents and cause the sprinkler to fail  
to operate in a fire situation or cause  
it to operate prematurely.
Worldwide 
Contacts
www.tyco-fire.com
General 
Description
The TYCO Model SW-20 and SW-24, 
11.2 K-factor, Extended Coverage Ordi-
nary Hazard (ECOH) Horizontal Sidewall 
Sprinklers, Standard Response are dec-
orative glass bulb sprinklers designed 
for use in ordinary hazard occupancies 
per NFPA 13.
The SW-20 provides protection of cov-
erage areas up to 16 ft. x 20 ft. (320 
ft
2
), whereas the SW-24 provides pro-
tection of coverage areas up to 16 ft. x 
24 ft. (384 ft
2
), as compared to standard 
coverage horizontal sidewall sprinklers 
having a maximum coverage area of 10 
ft. x 10 ft. (100 ft
2
) for ordi nary hazard 
occupancies.
Horizontal sidewall sprinklers are de-
signed for installation along a wall or 
the side of a beam and are common-
ly used instead of pendent or upright 
sprinklers due to aesthetics or building 
construction considerations, where pip-
ing across the ceiling is not desirable.
Corrosion resistant coatings, where 
applicable, are utilized to extend the 
life of copper alloy sprinklers beyond 
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the 
standard corrosion tests of the appli-
cable approval agencies, the testing is 
not representative of all possible cor-
rosive atmospheres. Consequently, it 
is recommended that the end user be 
consulted with respect to the suitability 
of these corrosion resistant coatings for 
any given corrosive environment. The 
effects of ambient temperature, con-
centration of chemicals, and gas/chemi-
cal velocity, should be con sidered, as a 
minimum, along with the corrosive na-
ture of the chemical to which the sprin-
klers will be exposed.
NOTICE
The Model SW-20 and SW-24 Sprin-
klers described herein must be installed 
and maintained in compliance with this 
document and with the applicable stan-
dards of the National Fire Protection As-
sociation, in addition to the standards 
of any authorities having jurisdiction. 
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition. The 
installing contractor or sprinkler manu-
facturer should be contacted with any 
questions.
Sprinkler 
Identification 
Number (SIN)
TY5332 - SW-20 
TY5337 - SW-24 
TY5332 is a re-designation for C5332 
TY5337 is a re-designation for C5337
Technical 
Data
Approvals
UL and C-UL Listed 
(Refer to the Design Criteria Section)
Polyester coated sprinklers are UL and 
C-UL Listed as Corrosion Resistant 
Sprinklers
NYC under MEA 177-03-E
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K= 11.2 GPM/psi
1/2
 (161,3 LPM/bar
1/2
)
Temperature Rating
SW-20: 155°F (68°C) & 200°F (93°C) 
SW-24: 200°F (93°C)
Finishes
Refer to Table B
Physical Characteristics:
Frame ............................Bronze
Button............................Bronze
Sealing Assembly  . . . . . . . . . . . . . . . .  Beryllium 
Nickel w/ TEFLON
Bulb .............................. Glass
Compression Screw  . . . . . . . . . . . . . . . . . Brass
Deector..........................Bronze
SW-24
SW-20