Model SW-20 and SW-24 — 11.2 K-factor 
Extended Coverage Ordinary Hazard 
Horizontal Sidewall Sprinklers (Standard Response)
Page 1 of 6  AUGUST 2018  TFP230
IMPORTANT
Refer to Technical Data Sheet 
TFP2300 for warnings pertaining to 
regulatory and health information.
Always refer to Technical Data 
Sheet TFP700 for the “INSTALLER  
WARNING” that provides cautions 
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and 
installation can permanently damage 
a sprinkler system or its compo-
nents and cause the sprinkler to fail  
to operate in a fire situation or cause  
it to operate prematurely.
Worldwide 
Contacts
www.tyco-fire.com
General 
Description
The TYCO Model SW-20 and SW-24, 
11.2 K-factor, Extended Coverage Ordi-
nary Hazard (ECOH) Horizontal Side-
wall Sprinklers, Standard Response 
are decorative glass bulb sprinklers 
designed for use in ordinary hazard 
occupancies per NFPA 13.
The SW-20 provides protection of cov-
erage areas up to 16 ft x 20 ft (320 ft
2
), 
whereas the SW-24 provides protec-
tion of coverage areas up to 16 ft x 24 
ft (384 ft
2
), as compared to standard 
coverage horizontal sidewall sprinklers 
having a maximum coverage area of 10 
ft x 10 ft (100 ft
2
) for ordi nary hazard 
occupancies.
Horizontal sidewall sprinklers are 
designed for installation along a wall 
or the side of a beam and are com-
monly used instead of pendent or 
upright sprinklers due to aesthetics or 
building construction considerations, 
where piping across the ceiling is not 
desirable.
Corrosion resistant coatings, where 
applicable, are utilized to extend the life 
of copper alloy sprinklers beyond that 
which would otherwise be obtained 
when exposed to corrosive atmo-
spheres. Although corrosion resistant 
coated sprinklers have passed the 
standard corrosion tests of the appli-
cable approval agencies, the testing is 
not representative of all possible cor-
rosive atmospheres. Consequently, 
it is recommended that the end user 
be consulted with respect to the suit-
ability of these corrosion resistant 
coatings for any given corrosive envi-
ronment. The effects of ambient tem-
perature, concentration of chemicals, 
and gas/chemical velocity, should be 
con sidered, as a minimum, along with 
the corrosive nature of the chemical to 
which the sprinklers will be exposed.
NOTICE
The Model SW-20 and SW-24 Sprin-
klers described herein must be installed 
and maintained in compliance with this 
document and with the applicable stan-
dards of the National Fire Protection 
Association, in addition to the stan-
dards of any authorities having juris-
diction. Failure to do so may impair the 
performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and 
devices in proper operating condition. 
The installing contractor or sprinkler 
manufacturer should be contacted with 
any questions.
Sprinkler 
Identification 
Number (SIN)
TY5332 - SW-20 
TY5337 - SW-24 
TY5332 is a re-designation for C5332 
TY5337 is a re-designation for C5337
Technical 
Data
Approvals
UL and C-UL Listed 
(Refer to the Design Criteria Section)
Polyester coated sprinklers are UL and 
C-UL Listed as Corrosion Resistant 
Sprinklers
NYC under MEA 177-03-E
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K= 11.2 GPM/psi
½
 (161,3 LPM/bar
½
)
Temperature Rating
SW-20: 155°F (68°C) & 200°F (93°C) 
SW-24: 200°F (93°C)
Finishes
Refer to Table B
Physical Characteristics:
Frame ............................Bronze
Button............................Bronze
Sealing Assembly  . . . . . . . . . . . . . . . .  Beryllium 
Nickel w/ TEFLON
Bulb .............................. Glass
Compression Screw  . . . . . . . . . . . . . . . . .  Brass
Deflector. . . . . . . . . . . . . . . . . . . . . . . . . . Bronze
SW-24
SW-20