Model AV-1-300 Alarm Check Valve, 300 psi (20,7 bar)
2-1/2, 4, 6, & 8 Inch (DN65, DN100, DN150 & DN200)
Vertical or Horizontal* Installation
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Email: techserv@tycofp.com
Page 1 of 22 OCTOBER 2009 TFP910
General
Description
The Tyco
®
Model AV-1-300 Alarm
Check Valves are divided seat ring,
rubber-faced clapper, waterflow alarm
check valves that are intended for use
in wet pipe (automatic sprinkler) fire
protection systems. They may be in-
stalled vertically or horizontally*, and
they are designed to automatically ac-
tuate electric and/or hydraulic alarms
when there is a steady flow of wa-
ter into the system that is equivalent
to the discharge rate of one or more
sprinklers.
A separately ordered Model RC-1 Re-
tard Chamber (TFP920) is required for
installations subject to variable pres-
sures. It is used to help prevent false
alarms associated with pressure vari-
ations in public water supplies.
The AV-1-300 Alarm Check Valve Trim
includes pressure gauges to moni-
tor system pressure conditions, a by-
pass check valve, a main drain valve,
and an alarm test valve. The bypass
check valve reduces the pos sibility of
false alarms by permitting slow as well
as small transient in creases in water
supply pressure to be passed through
to the system without opening the wa-
terway clapper.
NOTICE
The Model AV-1-300 Alarm Check
Valves described herein must be in-
stalled and maintained in compliance
with this document, as well as with the
applicable standards of the National
Fire Protection Association, in addi-
tion to the standards of any authori-
ties having jurisdiction. Failure to do
so may impair the integrity of these
devices.
The owner is responsible for maintain-
ing their re protection system and
de vices in proper operating condition.
The installing contractor or manufac-
turer should be contacted relative to
any questions.
* 4, 6, and 8 Inch (DN100, DN150, and DN200) Valve Sizes
Nominal
Valve Size
End Connections Available
Inlet x Outlet
Groove x Groove Flange x Groove Flange x Flange
2-1/2 Inch
(DN65)
22 lbs.
(10,0 Kg)
28 lbs.
(12,7 Kg)
N/A
4 Inch
(DN100)
45 lbs.
(20,4 Kg)
51 lbs.
(23,1 Kg)
62 lbs.
(28,1 Kg)
6 Inch
(DN150
68 lbs.
(30,9 Kg)
78 lbs.
(35,4 Kg)
93 lbs.
(42,2 Kg)
8 Inch
(DN200)
129 lbs.
(58,6 Kg)
148 lbs.
(67,1 Kg)
167 lbs.
(75,8 Kg)
Question and Answer IconNeed help?

Do you have a question about the Tyco AV-1-300 and is the answer not in the manual?

Tyco AV-1-300 Specifications

General IconGeneral
ModelAV-1-300
CategoryControl Unit
Output Voltage24 VDC
Dimensions6.5 x 4.5 x 2.5 inches
Operating Temperature32°F to 122°F (0°C to 50°C)
Weight0.9 kg (2.0 lbs)

Summary

General

General Description

Overview of the Model AV-1-300 Alarm Check Valve's function and intended use in fire protection systems.

Technical Data

Technical System Specifications

Details approvals, working pressure range, friction loss, and physical characteristics of the AV-1-300 valve.

Operation

Design Criteria

Installation

Setting Procedure

Care and Maintenance

Inspection Procedure

Quarterly inspection steps recommended for the AV-1-300 Alarm Check Valve to ensure proper alarm function.

False Alarms

Intermittent Alarms

Loss of Excess System Pressure

Excess Pressure Due To Thermal Expansion

Limited Warranty

Ordering Procedure

Valve Configurations

Guide to specifying standard, special order, and other AV-1-300 alarm check valve configurations.

Valve Trims and Accessories

Information on ordering available valve trims and necessary accessories like the RC-1 Retard Chamber.