EasyManua.ls Logo

Tyco DigiTrace 920 Series - Page 82

Tyco DigiTrace 920 Series
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82
Point Setup Sub-Menu
Parameter Factory User
Tag TAG-(factory ID)
Switch Control Mode Proportional
Prop Band 4°F (2°C)
Deadband
*n/a (5°F(3°C))
Cycle Time *n/a (10 min)
Switch Rating 30.0 A
Circuit Breaker 30.0 A
Max Power 7200 W
3 Ph Pwr Calc No
TS Fail Mode Off
TS CTL Mode TS1-Fail Off
TS 1 Type 100
Ω Plat
TS 1 Lead Resist *n/a (0
Ω)
TS 1 Hi Limit Disable
TS 2 Type 100
Ω Plat
TS 2 Lead Resist *n/a (0
Ω)
TS 2 Hi Limit Disable
Volt Source Pt A (or Pt B)
Fixed Volt *n/a (120V)
Volt Turns Ratio 1.00 to 1
Current Turns Ratio 1.00 to 1
Autocycle Enable
Autocycle Interval 8
Autocycle Units Hours
Override Source Remote
Load Shedding Disable
Common Setup Sub-Menu
Parameter Factory User
Temperature Units °F
Version V3.2x.xx n/a
Ext. Input Not used
Ext. Output Not used
Flash Alarm Output Yes
Alarm Output N.C.
Language English
Point B Used Yes
Passcode 0
Scroll Delay 0.15 secs
Copy Config… (see user manual)

Table of Contents