Appendix A of TFP1090 (07/2020) 
Summary Instructions (if problems occur, consult full document) 
DN65 and DN80, Model DPV-1 Dry Pipe Valve with Three-Way Alarm Test Valve, 
without Model ACC-1 Accelerator
A
M
L
E
K
J
N
H
F
B
G C D P
I.  Normal Conditions
• 
The Main Control Valve (A) is opened 
and locked.
• 
The sprinkler system is lled with air 
and is pressurized.
• 
The Main Drain Valve (F), and Low 
Body Drain Valve (L) are closed.
• 
The Three-Way Alarm Control Valve 
(E) is in the open position.
•  The Pressure Gauge Valves (B) and 
(C) are open.
• 
The Pressure Switch Valve (J) is 
open.
•  The Air Supply Control Valve (K) is 
open.
• 
System Air Pressure Gauge (G) 
reads downstream air pressure.
• 
Water Supply Pressure Gauge (H) 
reads the upstream water pressure.
II.  Operation
When one or more sprinklers are acti-
vated, air pressure is reduced down-
stream of the Dry Pipe Valve. When the 
air pressure is sufciently reduced, the 
water pressure overcomes the differen-
tial holding the Dry Pipe Valve closed 
and the Dry Pipe Valve opens to per-
mit water ow into the system piping 
and to be discharged from any open 
sprinklers. Also, with the Dry Pipe 
Valve open, water ows through the 
Alarm Port at the rear of the Dry Pipe 
Valve to actuate the Waterow Pressure 
Alarm Switch (M) and, as applicable, 
the Water Motor Alarm.
III.  Removing System From Service
Step 1. 
Close the Main Control Valve 
(A), close the Air Supply Control Valve 
(K), and place the Three-Way Alarm 
Control Valve (E) in the closed position.
Step 2. 
Drain the system with the Main 
Drain Valve (F) and by opening all auxil-
iary drain valves in the system to make 
sure that cross-mains and branch lines 
are drained.
IV.  Placing the System Back in 
Service
Step 1. 
Close the auxiliary drain valves 
after water ceases to discharge, and 
leave the Main Drain Valve (F) open.
Step 2. 
Place the Three-Way Alarm 
Control Valve (E) in the open position.
Step 3. 
Replace the sprinklers that 
have operated and the sprinklers close 
to the re.
Step 4.  Push down on the reset knob 
(P) to allow the Dry Pipe Valve (D) to 
re-seat.
Step 5. 
Via the Air Supply Control 
Valve (K), pressurize the system with 
air to 0,7 bar, and then open and close 
each auxiliary drain valves in the sys-
tem piping to drain any remaining water 
in trapped sections. Also, partially open 
the Low Body Drain Valve (L) to assure 
that the riser is completely drained. 
Close the Low Body Drain Valve (L) as 
soon as water ceases to discharge.
Step 6. 
Open the Air Supply Control 
Valve (K) to restore the system to the 
normal system air pressure.
Step 7. 
Partially open the Main Control 
Valve (A), and then slowly close the 
Main Drain Valve (F).
Step 8. 
Fully open the Main Control 
Valve (A) and lock it open.
Step 9. 
Reset the re alarm panel and 
notify the central alarm station.
V.  Weekly Test
Important: Prior to closing any valves 
or activating any alarms, notify local se-
curity guards and the central alarm sta-
tion if applicable.
Step 1. 
Place the Three-Way Alarm 
Control Valve (E) in the test position, 
verify that the alarm signal created by 
the Waterow Pressure Alarm Switch 
(M) is visible at the re panel. If appli-
cable, check the sound of the Water 
Motor Alarm — it must be clear and 
steady.
Step 2. 
Place the Three-Way Alarm 
Control Valve (E) in the open position 
and verify that the normal supply and 
system pressures are restored. If the 
supply pressure is below the normal, 
use the instructions from the water sup-
ply to obtain the usual pressure.
Step 3. 
Close the Pressure Switch 
Valve (J) and verify operation of the low 
air pressure Alarm Switch (N).
Step 4. 
Return the Pressure Switch 
Valve (J) to the normally open position 
after verifying that the alarm signal is 
visible at the re panel.