EasyManua.ls Logo

Tyco MULTIMATIC F470H User Manual

Tyco MULTIMATIC F470H
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
DELUGE VALVE,HORIZONTAL
MODEL F470H MULTIMATIC
®
4 and 6 INCH (100 and 150 mm)
GENERAL DESCRIPTION
The 4 and 6 inch (100 and 150 mm),
Model F470H Horizontal Multimatic
Deluge Valves are differential latch
type valves designed for fire protection
system service. They are used as
“automatic water control valves” in del-
uge, preaction, and foam-water fire
protection systems.The F470H Valves
also provide for actuation of fire alarms
upon system operation.
Operation of an F470H Valve is pro-
vided by an actuation (detection) sys-
tem that is separate from the normally
dry system piping. Trim configuration
options for automatic operation of the
F470H include wet pilot actuation, dry
pilot actuation, and electric actuation.
The various trim arrangements also
provide for local emergency (manual)
release of the F470H Valves.
APPROVALS AND STANDARDS
The 4 and 6 inch (100 and 150 mm),
Model F470H Horizontal Multimatic
Deluge Valves are listed by Underwrit-
ers Laboratories Inc. and Underwrit-
ers’ Laboratories of Canada. The
F470H Valves are also approved by
Factory Mutual Research Corporation.
The Model F470H Multimatic Deluge
Valves are accepted by the City of New
York under MEA 38-92-M.
WARNING
The Model F470H Horizontal Multi-
matic Deluge Valves described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards
of any other authorities having juris-
diction. Failure to do so may impair
the integrity of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. The installing contractor or
manufacturer should be contacted
relative to any questions.
Printed in U.S.A. 9-99
TD116H
Nominal Dimensions in Inches and (mm)
VALVE
SIZE
4
(100)
6
(150)
VALVE
SIZE
4
(100)
6
(150)
A
2"
NPT
2"
NPT
J
8.00
(203,2)
8.87
(225,3)
B
1/2"
NPT
1/2"
NPT
K
10.50
(266,7)
11.50
(292,1)
C
1/2"
NPT
1/2"
NPT
L
8.50
(215,9)
9.18
(233,2)
D
6.56
(166,6)
6.45
(163,8)
M
3.75
(95,3)
4.54
(115,3)
E
3.44
(87,4)
3.40
(86,4)
N
2.37
(60,2)
3.20
(81,3)
F
2.56
(65,0)
2.45
(62,2)
P
2.56
(65,0)
2.45
(62,2)
G
2.73
(69,3)
3.69
(93,7)
Q
1.72
(43,7)
1.82
(46,2)
H
5.25
(133,4)
6.63
(168,4)
R
13.25
(336,6)
14.25
(362,0)
6 INCH (150 mm)
VALVE ILLUSTRATED
FIGURE A
MODEL F470H HORIZONTAL MULTIMATIC DELUGE VALVES
DIMENSIONS AND PORT LOCATIONS
OBSOLETE
Question and Answer IconNeed help?

Do you have a question about the Tyco MULTIMATIC F470H and is the answer not in the manual?

Tyco MULTIMATIC F470H Specifications

General IconGeneral
ModelMULTIMATIC F470H
CategoryControl Unit
ManufacturerTyco
Input Voltage24 VAC
Dimensions60 mm

Summary

General Description

Approvals and Standards

Lists the approvals and standards the valve meets, including UL and FM.

Warning

Critical safety warning regarding installation and maintenance compliance.

Technical Data

Deluge Valve

Provides key specifications for the F470H Horizontal Multimatic Deluge Valve.

Valve Trim

Details the components included in different valve trim packages for operation.

Wet Pilot Actuation

Explains the Wet Pilot Actuation Trim and its detection system components.

Dry Pilot Actuation

Notes

Provides important notes and recommendations for the Dry Pilot Actuation system.

Electric Actuation Trim

Note

Offers a note regarding Factory Mutual approval for electric actuation.

Operating Principles

Installation

Outlines the criteria and recommendations for installing the F470H valve.

Valve Setting Procedure

Details the step-by-step process for setting the F470H valve initially or after operation.

Care and Maintenance

Annual Operation Test Procedure

Describes the annual procedure to verify the proper operation of the F470H valve.

Five Year Internal Valve Inspection

Specifies the recommended five-year inspection for the valve's diaphragm and internal parts.

Quarterly Solenoid Valve Test Procedure For Electric Actuation

Outlines the quarterly testing procedure for the solenoid valve in electric actuation systems.

Warranty

Ordering Procedure

Explains how to order the F470H valves, trims, and replacement parts.