Internet Alarm Communicator Installation Manual
[006] System Toggle Options 2
[1] Ethernet 1 receiver enabled. Default (ON).
ON: Ethernet receiver 1 is enabled.
OFF: Ethernet receiver 1 is disabled.
[2] Ethernet receiver 2 is enabled. Default (ON).
ON: Ethernet receiver 2 is enabled.
OFF: Ethernet receiver 2 is disabled.
[3]-[8] Reserved
[007] DNS Server IP 1
Default (000.000.000.000)
Programming this section is not permitted on a UL/ULC listed system.
Enter the IP address for DNS server 1. Format is 4 fields, each field is a 3 digit decimal. Valid
range: 000-255.
NOTE: If no value is programmed and DHCP is used, the DHCP server will configure the
address. If an address is programmed and DHCP is used, the address that you program
will be used instead of the DHCP address.
[008] DNS Server IP 2
Programming this section is not permitted on a UL/ULC listed system.
Default (000.000.000.000)
Enter the IP address for DNS server 2. Format is 4 fields, each field is a 3 digit decimal. Valid
range: 000-255.
NOTE: If no value is programmed and DHCP is used, the DHCP server will assign this value. If
an address is programmed and DHCP is used, the address that you program will be used
instead of the DHCP address.
Programming Options
[010] System Toggle Options 3
[1] Reserved.
[2] Visual verification. Default (OFF)
ON: Visual verification is enabled.
OFF: Visual verification is disabled.
[3] Reserved.
[4] Reserved.
[5] Reserved.
[6] Reserved.
[7] Reserved.
[8] Reserved.
[011] Installer Code
Default (CAFE)
Program the installer code for the communicator module. The installer code will be required when
programming the communicator module. Valid range: 0000 - FFFF.
[012] DLS Incoming Port
Default (0BF6/3062)
The DLS incoming local port (listening port) is the port DLS IV will use when connecting to the
communicator. If a router or gateway is used, it must be programmed with a transmission control
protocol (TCP) port forward for this port to the communicator module IP address. Valid range:
0000 - FFFF.
[013] DLS Outgoing Port
Default (0BFA/3066)
The DLS outgoing port is used for outgoing session to DLS IV after an SMS request has been sent
to the communicator. Use this section to set the value of the local outgoing port. The value must be
changed if the communicator is located behind a firewall and must be assigned a particular port