Valve Setting 
Procedure
Steps  1  through  10  are  to  be  per-
formed when initially setting the Mod-
el  DV-5  Deluge  Valve;  after  an  op-
erational  test  of  the  fire  protection 
system; or, after system operation due 
to a fire. Refer to Figure 4, 5, or 6, as 
applicable. 
Step 1. Close the Stop Valve (B). 
Step  2.  Close  the  Diaphragm  Sup-
ply  Valve (P).  For Dry  Pilot  Actuation, 
close  the  Dry  Pilot  Air  Supply  Valve 
(T). 
Step  3.  Open  the  Alarm  Test  Valve 
(G),  System  Drain  Valve  (E),  and  all 
auxiliary  drains  in  the  system.  Close 
the  auxiliary  drain  valves  after  water 
ceases to discharge. Leave the Alarm 
Test Valve (G) and System Drain Valve 
(E) open. 
At  this  time  make  certain  that  the 
Pressure Gauge Valves and the Alarm 
Control Valve (H) are open. 
Step  4.  Depress  the  plunger  of  the 
Automatic Drain Valve (F) to verify that 
it  is  open  and  that  the  DV-5  Valve  is 
completely drained. 
Step  5.  Clean  the  Diaphragm  Supply 
Strainer  (Q)  by  removing  the  clean-
out  plug  and  strainer  basket.  The  Di-
aphragm  Supply  Strainer  (Q)  may  be 
flushed  out  by  momentarily  opening 
the Diaphragm Supply Valve (P). 
Step 6. Reset the actuation system. 
Manual Actuation — Push the operat-
ing lever up; however, do not close the 
hinged cover at this time. 
Wet  Pilot  Actuation  —  Replace  oper-
ated  pilot  sprinklers  and/or  reset  the 
remote manual control stations. 
Dry  Pilot  Actuation  —  Replace  oper-
ated  pilot  sprinklers  and/or  reset  the 
remote manual control stations. Rees-
tablish dry pilot pneumatic pressure. 
Electric  Actuation  —  Reset  the  elec-
tric  detection  system  in  accordance 
with the manufacturer’s instructions to 
de-energize the solenoid valve. 
NOTE 
In  order  to  prevent  the  possibility  of 
a  subsequent  operation  of  an  over-
heated solder type pilot sprinkler, any 
solder  type  pilot  sprinklers  that  were 
possibly  exposed  to  a  temperature 
greater than their maximum rated am-
bient must be replaced. 
Step  7.  Open  the  Diaphragm  Supply 
Valve (P) and  allow time  for  full  pres-
sure to build up in the DV-5 Diaphragm 
Chamber. 
Step  8.  Operate  (open)  the  Manual 
Control Station (M) to vent trapped air 
from the DV-5 Diaphragm Chamber. If 
necessary, first open the hinged cover, 
and then fully pull down on the operat-
ing  lever.  SLOWLY  close  the  operat-
ing  lever,  by  pushing  it  up,  after  aer-
ated  water  ceases  to  discharge  from 
the Manual Control Station. Close the 
hinged  cover  and  insert  a  new  break 
rod  in  the  small  hole  through  the  top 
of the enclosing box. 
For  Wet  Pilot  Actuation,  crack  open 
the  Inspector’s  Test  Connection  and 
any  other  vent  valves  on  the  wet  pi-
lot line to relieve trapped air. After the 
discharge  of  air  has  stopped,  close 
the  vent  valves  and  the  Inspector’s 
Test Connection. 
Step  9.  Verify  the  ability  for  the  DV-
5  Diaphragm  to  hold  pressure  as 
follows: 
With the diaphragm chamber pressur-
ized per Step 8, temporarily close the 
Diaphragm Supply Valve (P), and then 
observe the Diaphragm Gauge (K) for 
a drop in pressure. 
If a drop in pressure is noted, the DV-
5 Diaphragm is to be replaced and/or 
any  leaks  must  be  corrected  before 
proceeding to the next step. 
If  the  Diaphragm  Chamber  Pressure 
Gauge  (K)  indicates  no  drop  in  pres-
sure,  re-open  the  Diaphragm  Sup-
ply Valve (P) and proceed to the next 
step. 
Step 10. Partially open the Stop Valve 
(B). Close the Alarm Test Valve (G) as 
soon  as  water  discharges  from  the 
System Drain Valve (E) and then close 
the  System  Drain  Valve  (E)  after  wa-
ter  ceases  to  drain.  Observe  the  Au-
tomatic  Drain  Valve  (F)  for  leaks.  If 
there are leaks, determine/correct the 
cause of the leakage problem. If there 
are  no  leaks, the  DV-5 Valve  is  ready 
to  be  placed  in  service  and  the  Stop 
Valve must then be fully opened. 
NOTES 
If  the  Alarm  Test  Valve  is  not  closed 
as soon as water discharges from the 
System Drain Valve, a false alarm may 
occur. 
When  the  Stop  Valve  (B)  is  opened, 
the  pressure  on  the  DV-5  Diaphragm 
Chamber may increase.  This  increase 
in pressure is normal, and if the pres-
sure  is  greater  than  16  bar,  the  pres-
sure  is  to  be  relieved  by  partially  and 
temporarily  opening  the  Manual  Con-
trol Station (M); however, do not allow 
the  pressure  as  indicated  on  the  Dia-
phragm  Gauge  (K)  to drop  below  the 
supply  pressure  shown  on  the  Water  
Supply Gauge (J), since this action may 
result in tripping of the DV-5 Valve. 
After  setting  a  fire  protection  system, 
notify  the  proper  authorities  and  ad-
vise  those  responsible  for  monitor-
ing  proprietary  and/or  central  station 
alarms.
TFP1338   Page 23 of 28