Tyco F3200 - Remote Relay & Open Collector Operation & Zone Mapping

Tyco F3200
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.DataSheet4U.com
Document No: LT0255 F3200/NDU AS4428.1 Installation Manual
Appendix A
Issue 1.04 30 June 2004 Page A-1
APPENDIX A1
COMPATIBLE ACTUATING DEVICES (DETECTORS)
The following detectors are compatible with the F3200 System. The maximum number of
detectors per circuit is indicated by the columns 4mA and IS, for Standard and Intrinsically
Safe applications. For IS application refer to Section 6.4.
DETECTORS CERTIFIED WITH F3200 FIP
MAX
NO.
TYPE DESCRIPTION BASE 4mA IS
MD614A HEAT DETECTOR TYPE A M614 40
-
MD614C HEAT DETECTOR TYPE C M614 40
-
MF614 IONISATION SMOKE DETECTOR M614 40
-
MR614 PHOTOELECTRIC SMOKE DETECTOR M614 40
-
MR614T PHOTOELECTRIC SMOKE DETECTOR M614 40*
1
-
MU614 CO FIRE DETECTOR M614 40
-
T614A HEAT DETECTOR TYPE A M614 40*
2
-
T614B HEAT DETECTOR TYPE B M614 40*
2
-
T614C HEAT DETECTOR TYPE C M614 40*
2
-
T614D HEAT DETECTOR TYPE D M614 40*
2
-
MF301Ex x IONISATION SMOKE DETECTOR M300 40
40
MR301Ex x PHOTOELECTRIC SMOKE DETECTOR M300 40
40
MR301TEx x PHOTOELECTRIC SMOKE DETECTOR M300 40
40
MS302Ex x INFRA-RED FLAME DETECTOR M300 40
40
S111 x INFRA-RED FLAME DETECTOR (IS) - 40 35
S121 x INFRA-RED FLAME DETECTOR (IS) - 40 35
S131 x INFRA-RED FLAME DETECTOR (IS) - 40 35
S231i+ x INFRA-RED FLAME DETECTOR (IS) - - 11
S231i+ INFRA-RED FLAME DETECTOR AND ZAU401 - 5 5
S231f+ INFRA-RED FLAME DETECTOR AND ZAU401 - 5 -
S261f+ INFRA-RED FLAME DETECTOR - 40 -
SU0600 15V MCP - 40 -
*
1
For ambient temp < 30°C. Max Qty is 34 otherwise
*
2
47E resistor required between AZC+ and detector +ve. See PBG0116.
Table I MINERVA/THORN Detectors
DETECTORS CERTIFIED WITH F3200 FIP
MAX
NO.
TYPE DESCRIPTION 4mA
DCA-B-60R HEAT DETECTOR TYPE A 40
DCA-B-90R HEAT DETECTOR TYPE C 40
DCD-A HEAT DETECTOR TYPE A WITH YBO – R/4A BASE 40
DCD-C HEAT DETECTOR TYPE C WITH YBO – R/4A BASE 40
DFE-60B (DFB-60B) HEAT DETECTOR TYPE B 40
DFE-90D (DFB-90B) HEAT DETECTOR TYPE D 40
DFJ-60B HEAT DETECTOR TYPE B WITH YBO – R/4A BASE 40
DFJ-90D HEAT DETECTOR TYPE D WITH YBO – R/4A BASE 40
SIJ-ASN IONISATION SMOKE DETECTOR WITH YBO – R/4A BASE 40
SLR-AS PHOTOELECTRIC SMOKE DETECTOR WITH YBO – R/4A BASE 40
SIF-AM IONISATION SMOKE DETECTOR 40
SIH-AM IONISATION SMOKE DETECTOR 40
SLK-A PHOTOELECTRIC SMOKE DETECTOR 40
SLG-AM PHOTOELECTRIC SMOKE DETECTOR 40
HF-24A ULTRAVIOLET FLAME DETECTOR 18
WITH YBC-RL/4AH4, YBF-RL/4AH4 OR YBF-RL/4AH4M BASES
Table II HOCHIKI Detector Range

Other manuals for Tyco F3200

Related product manuals