Document No: LT0255 F3200/NDU AS4428.1 Installation Manual
System Specifications
Issue 1.04 30 June 2004 Page 3-15
3.5 OUTPUT SPECIFICATIONS
3.5.1 8 ZONE MODULE OUTPUTS
Type Darlington open collector, switch to 0V
Voltage Rating 28.5V max, "off" state
1.1V max at 100mA “on” state
Current Rating 100mA max per O/P, 0.6A max per module, 1A max per FIP.
Transient Protection Allows external wiring
Terminations 8 Way demountable screw terminal, 1.5sq mm max. cable
Operation Programmable
Default O/C 1 = Zone 1 Alarm
O/C 2 = Zone 2 Alarm, etc.
3.5.2 8 RELAY MODULE OUTPUTS
Form 1 Pole changeover contacts
Voltage-free when unsupervised
Termination Demountable screw terminals, 1.5sq mm max cable
Rating 30V, 1Adc inductive , 30V, 2Adc resistive
Note
The relays are 2 pole, with the second pole terminated on PCB pads.
Operation Programmable
Supervision Ref. 3.4.4.
Looping Terminals 2 Sets of 4 joined voltage-free terminals per module
3.5.3 MAF/PSU OUTPUTS
Brigade Relays
Standby Normally energised, De-energises on battery fail or panel fail
Fault, Isolated, Alarm Normally de-energised, Energise on active state
Form 1 Pole voltage-free changeover contacts
Termination Demountable screw terminals
1.5sq mm max cable
Rating 30V, 3Adc inductive, 30V, 5Adc resistive
Isolation 1500V rms contact to coil