F3200/NDU AS4428.1 Installation Manual Document No: LT0255
System Specifications
Page 3-16 30 June 2004 Issue 1.04
MAF/PSU OUTPUTS (CONTINUED)
Ancillary & Bells
Anc 1, Anc 2 1 Pole voltage-free changeover contacts
Termination Demountable screw terminals, 1.5sq mm max cable
Rating 30V, 1Adc inductive, 30V, 2Adc resistive
(Note: The relays are 2 pole, with second pole terminated on PCB pads).
Operation Programmable (refer Programming Manual)
Default (Anc 2 is External Bell)
Supervision Separate terminal (ref 3.4.2)
Anc 3/Bells 2 pole relay
Link selectable function
Standard Format Polarity reversal, switched 24Vdc output
2 terminals, Bells +, -
Demountable screw terminals, 1.5sq mm max cable
Option 1 Pole voltage-free changeover contacts
Snip Links Lk2, 3, 4.
Rating 30V, 2Adc resistive, 30V, 1Adc inductive
Operation Programmable (refer Programming Manual)
Default Warning System
Supervision On Bells +, - terminals only (ref Section 3.4.2)
Power Supply Outputs
0Vdc
Termination 1 non-demountable screw terminal, 4sq mm max cable
2 demountable screw terminals, 1.5sq mm max cable
1 2.8mm tab terminal (LED Display)
Battery Backed DC Supply
Rating 27.3Vdc (24V battery nom), 2Adc, fused.
+VBF1 1 non-demountable screw terminal, 4sq mm max cable
1 demountable screw terminal, 1.5sq mm max cable
+VBF2 1 non-demountable screw terminal, 4sq mm max cable
1 demountable screw terminal, 1.5sq mm max cable
1 2.8mm tab terminal (LED Display)
Non-Battery Backed DC Supply
Rating 28Vdc nom, 2Adc, fused