EasyManua.ls Logo

Tyco F3200 - Page 39

Tyco F3200
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.DataSheet4U.com
Document No: LT0255 F3200/NDU AS4428.1 Installation Manual
System Specifications
Issue 1.04 30 June 2004 Page 3-17
MAF/PSU OUTPUTS (CONTINUED)
+VNBF 1 non-demountable screw terminal, 4sq mm max cable
1 demountable screw terminal, 1.5sq mm max cable
RZDU Comms
Tx, Rx, 0V 3 Wire (+VBF2 available for 4
th
wire)
Transmission Rate 1200 Baud
Protocol Vigilant F4000
Termination Demountable screw terminals, 1.5sq mm max cable
3.5.4 CONTROLLER/DISPLAY OUTPUTS
Spare Parallel Outputs (not fitted)
Number, Rating 6, CMOS 0-5V
Termination 10 Way FRC PCB header, J10
Serial I/O
Printer/Programmer Port (This is same port as Serial Port 0)
Form Pseudo RS232, Rx, Tx, 0V signals only
Transient Protection Allows external wiring
Transmission Rate 9600 Baud
Protocol ASCII Xon, Xoff
Termination 4 Way .156" male Molex (J1),
9 Way Miniature D available via
LM0041.
Female Pins (socket)
Pin 2 3 5 1 4 6 7 8
Tx Rx 0V └──┴──┘ └──┘
25 Way Miniature D available via LM0042
Female Pins (socket)
Pin 2 3 7 6 8 20
Rx Tx 0V └──┴──┘
Also available as 9 way male D connector (J27)
Serial Port 0 10 Way FRC header, J2
UART signals: RXD, TXD, RTS-, CTS-, DCD-
5V levels; 0V, +5V, +24V also available
Network 1 10 Way FRC header, J7
Network 2 10 Way FRC header, J9
UART signals for Network 1/2
RXD, TXD, RTS-, CTS-, DCD-
5V levels; 0V, +5V, +24V also available